Technical Manual
Generator Excitation Driver Module
easYgen | exciter-10
Software Version 1.01
Document ID: B37910, Revision B - Build 50683
easYgen Expansion Module
Страница 1: ...Technical Manual Generator Excitation Driver Module easYgen exciter 10 Software Version 1 01 Document ID B37910 Revision B Build 50683 easYgen Expansion Module...
Страница 2: ...ual in English Designed in Germany Woodward GmbH Handwerkstr 29 70565 Stuttgart Germany Telephone 49 0 711 789 54 510 Fax 49 0 711 789 54 101 E mail stgt info woodward com Internet http www woodward c...
Страница 3: ...tion Excitation easYgen Genset control Active Voltage Regulator with AVR logic Sensing current module command Fig 1 Overview easYgen 3500XT with easYgen exciter 10 The easYgen exciter 10 is equipped w...
Страница 4: ...The following parts are included in the scope of delivery Please check prior to the installation that all parts are present Fig 2 Dimension easYgen 3500XT with easYgen exciter 10 The following parts a...
Страница 5: ...6 35 mm 0 25 are needed which are not included QR Code To get access to the complete product documentation please scan this QR code or use the following link http wwdmanuals com easygenexciter 10 5 ea...
Страница 6: ...2 2 PMG power supply 14 2 2 3 Shunt power supply 15 2 2 4 Auxiliary winding power supply 16 3 Configuration 17 3 1 Configuration via easYgen 17 4 Operation 21 4 1 Current limitation IEXC 21 4 2 LED St...
Страница 7: ...an immediately dangerous situation that could cause death or severe injuries if not avoided WARNING This combination of symbol and signal word indicates a possibly dangerous situation that could cause...
Страница 8: ...in Figures All dimensions shown with no units specified are in mm 1 2 1 Copyright And Disclaimer Disclaimer All information and instructions in this manual have been provided under due consideration o...
Страница 9: ...s 1 2 2 Service And Warranty Our Customer Service is available for technical information For regional support please refer to http www woodward com Support_pgd aspx In addition our employees are const...
Страница 10: ...shall be mounted in such a way that optimal convection through the heat sink is ensured DANGER To avoid damages in case of a voltage control loop failure ensure that the engine will stop immediately a...
Страница 11: ...9 REV A Made in Taiwan Fig 3 Dimension easYgen 3500XT with easYgen exciter 10 2 2 Setup Connections Wire sizes Field wiring shall be made with use of cables which have temperature rating not less than...
Страница 12: ...ion Notes X1 X2 Z1 Z2 Power supply PMG input Shunt input or Auxilary winding input 40 250 Vac 40 500 Hz Note for Shunt and Auxiliary winding supply If the build up voltage is below 20Vac a reliable st...
Страница 13: ...PE 2 2 1 Wiring easYgen exciter 10 easYgen The figure below shows a typical wiring between the easYgen exciter 10 and the easYgen In this example analog output 2 of the easYgen is configured for AVR...
Страница 14: ...the wiring for PMG power supply PMG Configuration Stator 12 wire Marked T1 to T12 Z2 X1 Z1 X2 F F PMG F F T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 T1 Fig 6 Wiring for PMG power supply 14 easYgen exciter 10...
Страница 15: ...voltage cannot be guaranteed The figure below shows the wiring for Shunt power supply Stator 12 wire Marked T1 to Shunt Configuration Z2 X1 Z1 X2 F F T4 T5 T6 T10 T11 T12 F F T1 T2 T3 T7 T8 T9 Fig 7 W...
Страница 16: ...guaranteed The figure below shows the wiring for Auxiliary Winding power supply AUX Windings Configuration Z2 X1 Z1 X2 F F Stator 12 wire Marked T1 to T12 F F T4 T5 T6 T10 T11 T12 T1 T2 T3 T7 T8 T9 Fi...
Страница 17: ...er to chapter operation 4 1 Current limitation IEXC 3 1 Configuration via easYgen This document contains only two screenshots of important AVR parameters For detailed description of the configuration...
Страница 18: ...on the AVR button in the lower left corner you will get to the AVR page below There are some indications of actual values and the parameters for Voltage filter time Start behavior V f characteristic...
Страница 19: ...e output 2 is used to control the exciter The following screenshot shows an example of how to configure AO2 Note The hardware and source level settings influence the excitation range and control behav...
Страница 20: ...Fig 11 Configuration Analog Output 2 for AVR operation 20 easYgen exciter 10 B37910 3 Configuration 3 1 Configuration via easYgen...
Страница 21: ...the supply voltage and the PWM The higher the supply voltage the higher the limited current If current limiting is desired the potentiometer setting must be determined empirically because of the above...
Страница 22: ...e 3 C If temperature protection is triggered the green LED is turned off and red LED is illuminated until protection is deactivated PWM signal monitoring When the initial voltage is established the Ex...
Страница 23: ...iter 10 PART NO 10 012 909 REV B Made in Taiwan Fig 13 Product label for reference only The serial number is for this device not part of the product label but printed on the housing 23 easYgen exciter...
Страница 24: ...PWM Shield Fuse1 X1 X2 IEXC O peration Protection Fuse2 Z1 Z2 140 5 51 175 6 89 200 7 87 115 4 53 60 2 36 19 0 75 Unit mm inch 6 5 0 26 PART NO 10 012 909 REV A Made in Taiwan Outline Drawing 24 easY...
Страница 25: ...upply voltage for details refer to 5 4 Maximum continuous field current output CE Max Continuous Field Current Output UL 4 A according to UL 6200 Max Forcing Field Current Output for 10 s 10 A Tempera...
Страница 26: ...e following Standards EN 61000 6 2 2005 Generic Standards Immunity for Industrial Environments EN 61000 6 4 2007 Generic Standards Emissions for Industrial Environments EN 61010 1 2010 Safety requirem...
Страница 27: ...ice series Genset Control not preferred for new design GGB Generator Group Breaker GOV speed Governor rpm regulator HMI Human Machine Interface e g a front panel with display and buttons for interacti...
Страница 28: ...Pickup Unit MOP Mains Operation in Parallel MCB Mains Circuit Breaker LDSS Load Dependent Start Stop operation V Voltage I Current P Real power Q Reactive power S Apparent power Sequencer A sequencer...
Страница 29: ...Index C Contact person 9 Customer Service 9 S Service 9 Symbols in the instructions 7 W Warranty 9 29 easYgen exciter 10 B37910 Index...
Страница 30: ...Woodward GmbH Handwerkstra e 29 70565 Stuttgart Germany Phone Fax stgt info woodward com 49 0 711 789 54 510 49 0 711 789 54 101...