Items
Parameters
Defaults
Description
Weekly
Daily
Time (Day)
1 to 31
1
»Monthly«: Select a week day
Sunday, to
Saturday
Sunday
»Weekly«: Select a week day
Time (hour)
0 to 24 h
0 (o'clock)
Define the start time (hour)
Time (minute)
0 to 59
0
Define the start time (minute)
Duration
0 to 30000 min
30 min
Select the duration for a scheduled run
4.2.4.4
Configure Breakers
[PARAMETER / Configure application / Configure breakers]
Items
Parameters
Defaults Description
Configure breakers
Manual mode ATS
Key switch
Auto switch
Default:
Key
switch.
Handling of the breaker in MAN mode.
Key switch: Opens/closes breaker with the
buttons.
Auto switch: The controller logic is used to
open/close the breaker and the related buttons
are disabled.
Closing time
0.0 to 10.0 s
5.0 s
Pulse width of generator switch ON.
Notes
This is the duration from the closing pulse for
GCB as well. If the time is configured to "zero"
the closing pulse acts as a steady pulse.
Opening time
0.0 to 60.0 s
3.0 s
Pulse width of generator switch OFF
Notes
This is the duration from the opening pulse for
GCB as well.
4.2.5
Configure Monitoring
4.2.5.1
Monitoring Generator
Monitoring Voltage
[PARAMETER / Configure monitoring / Generator / Voltage]
51
easYgen-400
B37884A
4 Configuration