The main menu opens.
2. ▷
Select »1 set parameters«
3. ▷
Enter a password for the parameter settings screen.
4. ▷
Press return.
Factory default: 0500
▶
First parameter from the list appears.
5. ▷
Navigate until the desired parameter can be edited e.g. using the »Right« button
6. ▷
Edit parameter.
7. ▷
Press the »Set/Confirm« button
▶
The parameter is updated immediately!
The settings can be saved to the device by pressing the »Write« button!
The editor screen is closed automatically after five minutes of inactivity.
The setting process is aborted immediately when pushing the »Stop« button!
4.2.3
Configure Measurement
Generator Settings
[PARAMETER / Configure measurement / Generator]
Items
Parameters
Defaults
Description
General generator settings
Monitoring
On
Off
On
On
Monitoring is enabled.
Off
Monitoring is disabled.
Generator poles
(2 to 64)
4
Number of generator poles. Used for calculating starter
rotation speed if no speed sensor is used.
Generator fail delay
time
(0.0 to 20.0) s
10.0 s
39
easYgen-400
B37884A
4 Configuration
4.2.3 Configure Measurement
Released