WAGO Digital Inputs/Outputs (2 ... 16 x DI/DO)
P/N
750-400
750-402
750-430
750-1405
# of DOs
2 x DO
4 x DO
8 X DO
16 X DO
P/N
750-501
750-504
750-530
750-1504
There is a maximum of 16 WAGO analog inputs and up to 4 WAGO analog outputs with
up to 32 WAGO digital inputs and 32 WAGO digital outputs or up to 4 IKDs.
For all configurations with WAGO devices at least one WAGO CANopen fieldbus
coupler 750-337 is required!
Configurable WAGO devices
If configurable WAGO devices are used, the mode of the terminal must be configured via
the PC software »Wago I/O Check«. This configuration cannot be done via easYgen
parameters. The easYgen parameters for the corresponding channels must be consistent
with the Wago configuration!
RTD device (750-451)
Configure this 8 channel device RTD (750-451) via the »Wago I/O-Check« with the
following process image:
The following types are not supported: Ni1000 (high resolution), Ni1000 (TK5000),
Pt1000 (EN 60751 high resolution), and 1200 Ohms.
Typ
Expected format
Pt100 (EN 60751)
default
Ni100 (EN 60751)
default
Pt500 (EN 60751)
default
Pt200 (EN 60751)
default
Ni1000 (TK6180, DN 43760)
default
Ni120 (Minco)
default
5000 Ohms
S5-FB250
Thermocouple device (750-458) for voltage measurement
There is no intuitive setting in the easYgen if a channel of the TC device (750-458) is
configured for voltage measurement. A special scaling of the easYgen parameters
“Sender value at display min..” and “Sender value at display max.” like in the table below
is required.
WAGO device
Voltage range
Configure the according easYgen parameter
“Sender value at display
min.”
“Sender value at display
max.”
+/- 30 mV
-614.4
614.4
+/- 60 mV
-307.2
307.2
731
easYgen-3000XT Series
B37574
6 Application Field
6.3.10 Setup Expansion Modules at CAN 2
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...