3.3.4
Charging Alternator
General notes
The charging alternator D+ acts as an pre-exciting output during the engine start-up.
During regular operation, it acts as an input for monitoring the charging voltage.
Schematic and terminals
Fig. 23:
Charging alternator - wiring
Terminal
Description
A
63
Battery B+ (8 to 40.0 Vdc SELV)
B
65
Auxiliary excitation (D+) output
Table 3: Charging alternator - terminal assignment
3.3.5
Voltage Measuring
General notes
Woodward recommends protecting the voltage measuring inputs with slow-acting fuses
rated for 2 to 6 A.
The wide range terminals allow several voltages. The current voltage (range) of the
application must be "told" to the genset controller device. Settings are described in
chapter
╚═▷ “4.6 Configure Measurement”
.
NOTICE!
The maximum permissible voltage against ground connected on the easYgen is 300 Volt.
This is to consider if phase voltages are grounded.