Incrementing and comparing with an AnalogManager
Fig. 209:
screen shot HMI: AM increment sample
Acronym
Name
Value
A1
Analog input 1
Number:
91.03
Name:
Internal value 3
Value:
25.0000
A2
Analog input 2
Number:
10.01
Name:
ZERO
Value:
0
C1
Analog constant input
Value: 1.000
L1
Boolean input 1
Number:
07.28
Name:
Time dependent voltage
Value:
Result of LM 07.28
L2
Boolean input 2
Number:
09.07
Name:
Discrete input 7
Value:
Result of LM 09.07
O1
Operator 1
L1 [passed]
O2
Operator 2
L2 [passed]
Type
Operation type
INCREMENT
BR
Boolean result
A1≧ A2 + (n[L1] x C1)*
*) Reset if L2 = TRUE
(available as boolean result »91.02 AM Internal value 2«)
AR
Analog result
A2 + (n[L1] x C1)*
*) Reset if L2 = TRUE
(available as analog result »91.02 AM Internal value 2«)
657
easYgen-3000XT Series
B37574
4 Configuration
4.9.1 Operations
Released