Parameter
Navigate to [Parameter / Configuration / Configure monitoring / Miscellaneous / Other
monitoring / PV load reference].
ID
Parameter
CL
Setting range
[Default]
Description
8923
PV disconnect level
2
-20.0 to 20.0%
[-2.0%]
This is the system generator load
level on which the PV is
immediately to cut.
(Hysteresis is 0.5%.)
8924
Delay
2
0.1 to 99.0 s
[5.0 s]
If the system generator load level
underruns the disconnect level for
the delay time the alarm is
tripped.
(The delay off time is 0.08s.)
8925
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
8926
Self acknowledge
2
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
4.5.6.16 Multi-Unit Parameter Alignment
General notes
The multi-unit parameter alignment functionality requires that the relevant parameters
are all configured identically at all participating units.
If at least one of these parameters is configured different in at least one of the units, the
display indicates "Parameter alignment" on all units and the logical command variable
"08.16" will be enabled. To identify different configured units, please use the diagnostic
screen "Genset parameter alignment":
HMI: [Next Page / Multi-unit / Genset parameter alignment]
ToolKit: [STATUS MENU / Multi-unit / Genset parameter alignment]
577
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.16 Multi-Unit Parameter Alignment
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...