ID
Parameter
CL
Setting range
[Default]
Description
2420
Reset time pole slip
events
2
10 to 999 s
During released pole slip
monitoring and with a pole slip
counter which is not increased
anymore for this time, the pole
slip counter will be reset.
[60 s]
2421
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
Pole slip alarm class. Default
alarm class D opens the GCB and
stops the engine after cooldown
timer.
[Class D]
2422
Self acknowledge
2
Yes
Self-acknowledge pole slip alarm
[No]
2423
Mains decoupling by
pole slip
2
On
Use pole slip monitoring for mains
decoupling
[Off]
Alarm
The device indicates and stores the text "Pole slip" (ID2424).
Visualization
The device indicates "Pole slip events" in ToolKit (ID2425).
LogicsManager
The device provides the LM command variable "06.36 Pole slip" (10674).
AnalogManager
The device provides the AM variable "01.86 Number of pole slips" (9765).
4.5.2
Configure Engine Monitor
4.5.2.1
Engine Overspeed (Level 1 & 2) ANSI# 12
General notes
The speed measured by the magnetic pickup unit (MPU) is monitored for overspeed. If the
MPU is disabled, the speed may only be monitored using the generator overfrequency
monitoring. If the MPU speed exceeds the overspeed limits the configured alarms will be
initiated.
If this protective function is triggered, the display indicates "Overspeed 1" or "Overspeed
2" and the logical command variable "05.01" or "05.02" will be enabled.
╚═▷ “9.1.1 Triggering Characteristics”
for the triggering characteristic of this
monitoring function.
468
easYgen-3000XT Series
B37574
4 Configuration
4.5.2 Configure Engine Monitor
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...