ID
Parameter
CL
Setting range
[Default]
Description
This parameter is not valid in
A13
.
3408
Emerg. start with
MCB failure
2
[Yes]
No
Emergency power operations may
be configured with the failure of
the MCB in addition to a loss of
power on the mains supply.
Notes
An MCB breaker alarm is indicated
if parameter "MCB monitoring"
(parameter
configured "On".
This parameter is not valid in
A13
.
12200
Inhibit emerg.run
(Inhibit emerg. run)
2
Determined by LogicsManager
86.11
[(0 & 1) & 1]
= 10710
Once the conditions of the
LogicsManager have been fulfilled
the emergency power operation
will be terminated or blocked.
Notes
It is possible to interrupt an
already activated emergency run.
For information on the
LogicsManager and its default
settings see
.
This parameter is not valid in
A13
.
4101
Break emerg. in
critical mode
(Override emergency
operations in critical
mode)
2
0 to 999 s
[5 s]
The emergency power operations
are overridden for the configured
time when the critical mode starts
in order to supply the complete
generator power to the sprinkler
pump.
4.5
Configure Monitoring
Replacement: "Delayed by engine speed" becomes "Enabled"
Formerly (non-XT easYgen) several monitoring functions could be delayed each by use of
parameter "Delayed by engine speed". Exchanging it by the new parameter "Enabled"
introduces the one-change-switch of all monitoring functions by LogicsManager 11459
"87.70 LM: Release eng.mon.".
With software revision 1.13 or higher each monitoring LogicsManager can be enabled
alternatively by one of 32 Flags.
Factory settings ensure same behavior of each affected monitoring function as of non-XT
easYgen series before.
419
easYgen-3000XT Series
B37574
4 Configuration
4.5 Configure Monitoring