ID
Parameter
CL
Setting range
[Default]
Description
5777
LDSS sort priority
always
2
On
The priority is considered in each
moment.
The priority will be changed
depending on priority input and
running hours even with constant
load.
Notes
This parameter is only effective
if »Start stop mode« (parameter
) is configured
to »Reserve power«.
This feature can cause more start
and stop sequences, even there is
only one additional generator
brought into the LDSS system.
[Off]
The priority is depending on
priority input and running hours
but only considered, if the nominal
power in the system changes. The
nominal power changes when
another generator is to stop or to
start anyway.
Notes
This setting causes less generator
changes and brings more
calmness in the system.
5759
Minimum running
time
2
0 to 32000 s
[180 s]
If a genset has been started by
the LDSS function, it continues to
operate at least for this time even
if it would have been stopped
before.
This timer is started with the
closure of the GCB. If an
emergency run is active (
) and the
mains return, this timer will be
overridden and the load is
transferred back to the mains
after the mains settling time
(parameter
expired.
4.4.5.5.4
Islanded Parallel Operation (IOP)
General notes
In case of an islanded parallel operation (MCB open), the first genset will be connected to
the de-energized busbar.
At least one genset must be in operation in islanded operation.
403
easYgen-3000XT Series
B37574
4 Configuration
4.4.5.5.4 Islanded Parallel Operation (IOP)
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...