ID
Parameter
CL
Setting range
[Default]
Description
This value specifies the lower
frequency limit (negative value
corresponds to negative slip →
generator frequency is less than
the busbar frequency).
Notes
This parameter only applies to
application modes
A03
and
A04
.
5703
Max. positive phase
angle GCB
2
0.0 to 60.0°
[7.0°]
The prerequisite for a close
command being issued for the
GCB is that the leading phase
angle between generator and
busbar is below the configured
maximum permissible angle.
Notes
This parameter only applies to
application modes
A03
and
A04
.
This parameter is only displayed,
if parameter
is
configured to "Phase matching".
5704
Max. negative phase
angle GCB
2
-60.0 to 0.0°
[-7.0°]
The prerequisite for a close
command being issued for the
GCB is that the lagging phase
angle between generator and
busbar is below the configured
maximum permissible angle.
Notes
This parameter only applies to
application modes
A03
and
A04
.
This parameter is only displayed,
if parameter
is
configured to "Phase matching".
5707
Phase matching GCB
dwell time
2
0.0 to 60.0 s
[3.0 s]
This is the minimum time that the
generator voltage, frequency, and
phase angle must be within the
configured limits before the
breaker will be closed.
Notes
This parameter only applies to
application modes
A03
and
A04
.
This parameter is only displayed,
if parameter
is
configured to "Phase matching".
8825
Phase angle
compensation GCB
3
The phase angle between
generator voltage and generator
busbar voltage can be
compensated according to an
installed power transformer
between generator and busbar.
On
The compensation is active. The
phase will be compensated
according the value configured in
parameter
280
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.3 Configure Breakers: GCB
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...