ID
Parameter
CL
Setting range
[Default]
Description
12970
MAN engine start
2
Determined by LogicsManager
87.50
[(0 & 1) &1]
= 11439
With the rising edge of this
LogicsManager equation an
engine start command in
operating mode MANUAL is
initiated. The state TRUE of this
LM inhibits the start command in
MANUAL.
12971
MAN engine stop
2
Determined by LogicsManager
87.59
[(0 & 1) &1]
=11448
With the rising edge of this
LogicsManager equation an
engine stop command in
operating mode MANUAL is
initiated. The state TRUE of this
LM inhibits the start command in
MANUAL.
12999
Release eng.mon.
2
Determined by LogicsManager
87.70
[(02.34 Firing speed electr. &
02.35 Firing speed rpm) &
03.28 Start/Gas]
t
ON
= 0.00; t
OFF
= 0.00]
= 11459
Switch to activate the delayed
engine monitoring e.g., oil
pressure, under frequency, ...
Notes
For more details see description
below.
Release Engine Monitoring
This LogicsManager equation (ID = 12999 with logical command variable 11459) enables
or blocks all monitoring functions, which are speed related by enabled setting: “Delayed
by engine speed”:
• Under/Over frequency
•
• Under speed
•
• Under voltage
•
• ...
•
223
easYgen-3000XT Series
B37574
4 Configuration
4.4.1.2 Engine Start/Stop
Released