To connect this USB 2.0 (slave) device a USB cable with USB Type A (PC/laptop side) and
Type B (Woodward device side) connectors is necessary.
USB cable length shall be limited up to 3 m. It is recommended to use professional (high
quality) USB cable: 28AWG/1P+24AWG/2C with good shielding.
Use USB service port for ToolKit connection
The USB interface is a service port and the preferred ToolKit connection!
'Read only' USB interface
╚═▷ “3.4.1 Interfaces overview”
For others than ToolKit connection the USB interface is read-only!
It can be used for further service tasks from manufacturer's side.
Connecting it to a PC/laptop will display the USB interface available and all files prepared
from Woodward manufacturing side. Read/write attributes of this service port are
restricted to read only.
3.4.4
CAN Bus Interfaces
Avoid electrostatic discharge!
Avoid electrostatic discharge during cable connection to the unit.
Pin assignment
For location of interface 5 and 6 see
╚═▷ “3.4.1 Interfaces overview”
.
Fig. 78:
screwable 6-terminal connector - CAN bus
Terminal
Description
A
max
1
GND - local galvanically isolated
1.5 mm
2
113
easYgen-3000XT Series
B37574
3 Installation
3.4.4 CAN Bus Interfaces
Released