9.3.2
Logical Command Variables
9.3.2.1
Group 01: Global alarms
For the description of the alarm classes refer to chapter 'Alarm classes'.
HMI Text
Note
01.01 Alarm class A
TRUE as long as an alarm of alarm class A is active or
latched.
01.02 Alarm class B
TRUE as long as an alarm of alarm class B is active or
latched.
01.03 Alarm class C
TRUE as long as an alarm of alarm class C is active or
latched.
01.04 Alarm class D
TRUE as long as an alarm of alarm class D is active or
latched.
01.05 Alarm class E
TRUE as long as an alarm of alarm class E is active or
latched.
01.06 Alarm class F
TRUE as long as an alarm of alarm class F is active or
latched.
01.07 All alarm classes
TRUE as long as at least one alarm of the alarm classes
A/B/C/D/E/F is active or latched.
01.08 Warning alarm
TRUE as long as at least one alarm of the alarm classes A/B
is active or latched.
01.09 Shutdown alarm
TRUE as long as at least one alarm of the alarm classes
C/D/E/F is active or latched.
01.10 Centralized alarm
TRUE as long as at least one alarm of the alarm classes
B/C/D/E/F is active or latched.
01.11 New alarm triggered
TRUE if any alarm of the Alarm classes B/C/D/E/F has been
triggered until it is acknowledged.
9.3.2.2
Group 02: System conditions
HMI Text
Note
02.01 LM FALSE
Fixed value - often used for default setting
02.02 LM TRUE
Fixed value - often used for default setting
02.03 Gen. voltage ok
TRUE as long as the generator voltage is within the
operating range.
1084
easYgen-3000XT Series
B37574
9 Appendix
9.3.2 Logical Command Variables
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...