Chapter 4.
Entering Control Setpoints
Introduction
This chapter contains information on control calibration. It includes initial prestart-up and start-up settings
and adjustments, and a current transformer phasing procedure. Because of the variety of installations,
plus system and component tolerances, the 2301E-HT control must be tuned and configured for each
system to obtain optimum performance.
An improperly calibrated control could cause an overspeed or other
damage to the prime mover. To prevent possible serious injury from
an overspeeding prime mover, read this entire procedure before
starting the prime mover.
Control Assistant PC Interface
The connection of a computer is only required for calibration and setup of the 2301E-HT control on a
prime mover. The computer and Control Assistant software is not required and not necessary for normal
operation of the prime mover, unless Modbus is being used for monitoring.
Control Assistant was developed by Woodward to be a Servlink OpcServer client software product that
provides a generic PC interface to any control, and is a very powerful setup, testing, and troubleshooting
tool. Control Assistant provides a means of shutting down and placing the control in the I/O Lock mode for
Configuration, saving values in the control EEPROM and resetting the control. Application tunable values
can be uploaded, downloaded and saved to a file.
Figure 4-1. Control Assistant
An “inspector” provides a window for real-time monitoring and editing of all control Configuration and
Service Menu parameters and values. Custom “inspectors” can easily be created and saved. Each
window can display up to 28 lines of monitoring and tuning parameters without scrolling. The number with
scrolling is unlimited. Two windows can be open simultaneously to display up to 56 parameters without
scrolling. Tunable values can be adjusted at the inspector window. Control Assistant communicates to the
control through an RS-232 cable connection to the comm port which is configured as a point-to-point only
Servlink OpcServer.