Fire Deck
Service Manual
PG
20
OF
44
M0011.09 APRIL 2019
An ongoing program of product improvement may
require us to change specifications without notice.
WOOD STONE CORPORATION
1801 W. Bakerview Rd.
Bellingham, WA 98226 USA
TOLL FREE
800.988.8103
TEL
360.650.1111
FAX
360.650.1166
woodstone-corp.com
INFRARED BURNER TROUBLESHOOTING
Many Wood Stone ovens are equipped with an Underfloor Infrared (IR) Burner� The IR Burner is designed to assist the Radiant Burner
or the wood fire during start-up and during times of heavy usage� It is thermostatically controlled� It is not the primary heat source
for the oven� The IR Burner’s Gas Valve and Pilot/Igniter are identical to those used on the Radiant Burner�
RFG-IR Models
IR Burner is not lighting� The display
may be flashing “check”�
NOTE:
You will not see flame at the
black tubes on the front of the Burner�
CAUTION:
Never attempt to light this
Burner manually� To visually confirm
that the Burner is lit, look through the
gap next to the Pilot/Igniter�
Is the Radiant Burner running?
If not, proceed first with Radiant Burner
troubleshooting� See previous pages of this manual
NOTE:
On RFG-IR ovens, the IR Burner will not light until the Controller has
verification that the Radiant Burner has lit, or one of the Radiant Burners on ovens
with 2 Radiant Burners�
If the Radiant Burner is running, and the Controller is calling for IR heat, it will
allow the IR Burner 90 seconds to light� If the Burner has not lit after this time the
Controller will flash “check”� Turn the oven off and then back on to reset�
1.
If the Radiant Burner is running, is the Controller calling for heat, i�e� the Hearth
Temperature is lower than Hearth Set Point?
2.
Is the switch on the Honeywell Gas Control Valve in the “On” position?
3.
Visually check for Igniter glow� If the Igniter does not come on when the IR
Burner is called for, check that the MOLEX connectors are securely plugged
into the Gas Control Valve� Make sure that the pins are securely locked into the
connector body� Remove any wire ties and uncoil the Igniter wires so that there
is minimal contact between them� Check the continuity of the Glow Coil at the
two adjacent wires on the Igniter connector; this should be approximately 3�5
ohms� If the circuit is open, replace the Igniter� If Glow Coil tests OK, disconnect
the SV-1 wire harness from the Gas Valve and with the Controller calling for
heat, test for 24 volts between the yellow and white wires, and brown and white
wires� Do not test for voltage at the connectors on the Gas Valve; damage to
the Valve may result� If voltage is not present, see Controllers Troubleshooting
section of this manual� If voltage is present replace the Igniter� If there is still no
glow, replace the Gas Valve�
4.
If the Igniter is glowing and the gas supply to the oven is good, but Pilot is
still not lighting: Remove the Igniter and inspect for damage and/or a plugged
orifice� Replace if necessary� If Pilot orifice is not plugged or damaged, replace
Gas Valve�
Burner will not light or shuts off
sometimes, and, the Igniter wires
appear to be burned�
1.
Loose Pilot Tube: Tighten and replace Igniter�
2.
Inadequate oven venting or negative air pressure: See Installation and Operation
manual instructions� Call Wood Stone for information�
Probable Cause/Solution
Symptom
Содержание FIRE DECK 6045
Страница 41: ...PG 41 OF 44 M0011 09 APRIL 2019 Blank page ...
Страница 43: ...PG 43 OF 44 M0011 09 APRIL 2019 Blank page ...