Parameter settings
3066501_201910
WOLF GmbH | 57
7
Parameter settings
BM-2 programming unit installation and operating instructions for contractors
AM display module installation and operating instructions for contractors
7.1
Parameter list
i
Changes may only be made by a contractor or WOLF customer service.
NOTE
Improper use!
System faults.
► Arrange for a contractor to set and change parameters.
Parameters can only be displayed or changed using the BM-2 programming unit or the AM display
module.
Param-
eter
Description
Unit
Min.
Max.
Factory
setting
Individual
setting
HG01
Burner hysteresis
°C
7
30
15
HG07
HTG pump run-on (heating mode)
min
0
30
1
HG08
Maximum boiler water temperature HTG
T-Flowmax (applicable to heating mode)
°C
40
95
75
HG09
Burner cycle block (applies to heating mode) min
1
30
10
HG10
Bus address
-
1
5
1
HG13
Function input E1
(E1 for various functions)
-
Various Various
None
HG14
Function output A1 (230 VAC)
(A1 for various functions)
-
Various Various
None
HG15
Cylinder hysteresis
°C
1
30
5
HG16
Minimum heating circuit pump rate
%
15
100
45
HG17
Maximum heating circuit pump rate
%
15
100
100
HG19
CPP run-on time
min
1
10
4
HG20
Max. cylinder heating time
min 30/OFF
300
120
HG21
Minimum boiler temperature BTmin
°C
20
90
20
HG22
Maximum boiler temperature BTmax
°C
50
90
80
HG23
Maximum DHW temperature
°C
60
80
65
HG25
Excess boiler water temperature during
cylinder heating
°C
0
40
10
HG28
Enable burner stages
-
Various Various HTG 2 stage
DHW 2
HG33
Burner hysteresis runtime
min
1
30
10
HG34
eBus feed
-
Off
On
Auto
HG39
Soft start time
min
0
10
10
HG40
System configuration
-
Various Various
1
HG42
Header hysteresis
°C
0
20
5
HG43
No function
-
-
-
-
HG44
No function
-
-
-
-
HG45
No function
-
-
-
-
HG46
Excess boiler water temperature, header
°C
0
20
6
HG47
CO
2
setting
-
Variable Variable
Variable
HG49
CO
2
setting
-
Variable Variable
Variable
HG56
Input E3:
Only if I/O module is connected.
-
Various Various
None
HG57
Input E4:
Only if I/O module is connected.
-
Various Various
None
HG58
Output A3:
Only if I/O module is connected.
-
Various Various
None