Planning
3066501_201910
WOLF GmbH | 21
Fire protection
No clearance is required between the concentric balanced flue and combustible materials or components,
as temperatures above 85°C will not occur at the rated heating output.
Connection to the air/flue gas routing system
– It must be possible to inspect the entire cross-section of the flues.
– Therefore, install at least one appropriate cleaning and/or inspection port inside the boiler room; agree
on suitable arrangements with the local flue gas inspector.
– Between the flue outlet and the roof surface, there must be a clearance of at least 0.4 m.
Flue gas temperature limiter
The electronic flue gas temperature limiter switches the heat generator off when the flue gas temperature
exceeds 120°C. The heat generator restarts when the reset button is pressed.
Appliance connection with flue gas test port
The following applies to the connection with flue gas test port:
– Required for the proper operation of the heat generator
– Easily accessible by the chimney sweep
– Fitted to the heat generator at the factory
– Alternatively, install immediately after the 87° bend connected directly to the heat generator
i
If replacing a WOLF COB with a WOLF COB-2, reuse the existing connection with a flue gas test
port.
4.6.2
Overview of connection types
B23
B33
C53
C83x
C53x
C33x
IIIIIIIIII
IIIIIIII
IIIIIIIII
IIIIIIIII
IIIIIIIII
IIIIIIIII
IIIIIIII
IIIIIIIII
IIIIIIIII
IIIIIIIII
IIIIIIIII
III
IIII
IIII
IIIII
IIIIII
IIIII
IIIII
IIIII
IIIII
IIIII
IIIII
IIIIII
IIIIIIIIIIIIIIIIIII
C33x
C53x
C93x
C33x
B33
C93x
C43x
Fig. 4.4
Overview of connection types
q
Provide ventilation for B23, B33, C53