A3091000/A3091250
ProMIX™ 101 Radiant
Heating Reset Control

5

Power-up/Setup Display Sequence

This mode is entered on power-up or any time the Display or Reset Button is pressed while run-
ning. On power-up or reset, the settings scroll through automatically. To scroll manually, press the
Display button once. Then press it after each setting has been reviewed. If the display button is not
pressed for 60 seconds, the control will revert to scrolling automatically. All of the settings may be
adjusted while displayed.

Temperature Scale

(jumper-selectable)

Control Signal Output

(jumper-selectable)

Valve Action

(jumper-selectable)

Outdoor Air Low (Outdoor Design
Temperature) (potentiometer adjustable)

Outdoor Air High (Warm Weather Shutdown)

(potentiometer adjustable)

Primary Loop High (Minimum Return
Temperature) (potentiometer adjustable)

Secondary Loop High (Max. Radiant Loop
Temp.) (potentiometer adjustable)

Secondary Loop Low (Min. Radiant Loop
Temp.) (potentiometer adjustable)

Outdoor Air Temperature (Current Outdoor
Temp.) (sensor input)

Primary Loop Temperature (Current Return
Temp.) (sensor input)

Secondary Loop Temperature (Current Radiant
Temp.) (sensor input)

Continue in run mode
(if scrolling manually, press Display button to
continue)
Brief delay between modes

Fahrenheit
Celsius

0-10VDC
4-20mADC

Direct Acting closed at 0V, open at 10V)
Reverse Acting (closed at 10V, open at 0V)

°

F range

°

C range

°

F range (must be 

OAL+20)

°

C range (must be 

OAL+11)

°

F range

°

C range

°

F range

°

C range

°

F range (must be 

SLH-20)

°

C range (must be 

SLH-11)

°

F range

°

C range

Open sensor error
Shorted sensor error

°

F range

°

C range

Open sensor error
Shorted sensor error

°

F range

°

C range

Open sensor error
Shorted sensor error

t

°

F

°

C

Out

0.10
4.20

Act

dA
 rA

OAL

-60..41
-51..5

OAH

40..70
4..21

PLL

60..150
15..65

SLH

85..200
29..93

SLL

65..110
18..43

OA

-60..122
-51..50
Err..OPn
Err..Sht

PL

32..221
0..105
Err...OPn
Err...Sht

SL

32..221
0..105
Err...OPn
Err...Sht

run

...

Содержание A3091000

Страница 1: ...is compatible with other types of hydronic heat distribution systems where the use of a weather responsive control is desired Installation and Operating Instructions Features Provides outdoor reset co...

Страница 2: ...warmer the desired water tem perature The SL sensor provides feedback for the control loop To provide the proper temperature in the radiant loop the control positions the valve using a proportional in...

Страница 3: ...ete Design Assistance Manual SLH setting should never exceed the recommended water temperatures for the method in which the tubing is installed SLL The minimum radiant loop temperature should be set t...

Страница 4: ...with 18 22 AWG wire 4 Wire the control as indicated by the termi nal block labels or by the wiring schematic provided in Section 6 Be sure to provide an earth ground to the case 5 The ProMIX 101 Contr...

Страница 5: ...op High Max Radiant Loop Temp potentiometer adjustable Secondary Loop Low Min Radiant Loop Temp potentiometer adjustable Outdoor Air Temperature Current Outdoor Temp sensor input Primary Loop Temperat...

Страница 6: ...SLL SLS SLH F range C range Open sensor error Shorted sensor error Circulator boiler off valve closed blank if below 15 0 VAC OA 60 122 51 50 Err OPn Err Sht PL 32 221 0 105 Err OPn Err Sht SLS 65 110...

Страница 7: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 7 Typical Piping Arrangement using the Wirsbo ProMIX 101 Controller A B...

Страница 8: ...Heating Reset Control 8 Typical wiring using the ProMIX 101 Controller and a Wirsbo DT10 Thermostat Typical wiring using the ProMIX 101 Controller Wirsbo Zone Control Module and a Single Pump Relay to...

Страница 9: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 9 Typical wiring using the ProMIX 101 Controller with Wirsbo Zone Control Module...

Страница 10: ...A3091000 A3091250 ProMIX 101 Radiant Heating Reset Control 10 Typical wiring using the ProMIX Controller Wirsbo Zone Control Module and Multiple Pump Relay...

Страница 11: ...mperature is below OAL the SL temperature should be at its maximum SLH should not be increased above the maximum tempera ture limitation for the installation method 4 If the heat output is excessive a...

Страница 12: ...rculator N O relay contact switched line 12 22 AWG copper wire only HP 120 VAC Full Load 7 4 A Locked Rotor 43 2 A Resistive 10 A 3 Boiler Control Signal N O relay contract dry contacts limited to 18...

Отзывы: