Appendix
12.2
MODBUS Status Information
MODBUS-Specific Status
8
Standardized
Status 0
Standardized
Device
Malfunction
■
0x01
Simulation Active
The device is in simulation mode and one or more of its
device variables are not representative of the process.
■
0x02
Non-Volatile Memory Defect
The non-volatile memory check is invalid or corrupt, or the
battery of a battery-powered memory is defective.
■
0x04
Volatile Memory Defect
The RAM memory check is invalid or corrupt.
■
0x08
Watchdog Reset Executed
A watchdog reset has been executed.
■
0x10
Environmental Conditions Out Of Range
An internal or environmental condition is beyond acceptable
limits.
■
0x20
Power Supply Conditions Out Of Range
The power supply is outside its allowable range.
■
0x40
Electronic Defect
A hardware problem has been detected.
9
Standardized
Status 1
Not available
10
Analog Channel
Saturated
Not available
11
Standardized
Status 2
Standardized
Lists Changes
■
0x01
Instrument List Changed
When set, the gateway has lost communication with one of its
sub-devices or discovered a new sub-device. This bit is reset
if command 74 is issued. The current sub-device list is read
using command 84.
■
0x02
Duplicate Master Detected
The adapter has discovered another master with the same
address connected to its token-passing interface.
12
Standardized
Status 3
Not available
13
Analog Channel
Fixed
Not available
14 ... 24 Device-Specific
Status
Information
Not available
Byte
Parameter
Description
Code
Parameter
Description
0x01
(LSB)
Cache Validity
Set to 1 when the cache of the device for HART command 3 is
empty.
0x02
(LSB)
Identification
Ongoing
Set to 1 when the gateway is performing a device identification
procedure.
LSB: lower significant byte