SECTION 6
ELECTRICAL
6-4
NOTE: See 12-Volt Breaker Panel elsewhere in
this section.
110-VOLT RECEPTACLES
(OUTLETS)
A number of standard AC electrical outlets are
provided throughout the coach for connecting
small appliances such as televisions, radios,
toasters, etc. An outlet is also located on the
outside of the coach near the entrance door.
GROUND FAULT CIRCUIT
INTERRUPTER
Bath, galley and exterior outlets are connected
to a GFCI (Ground Fault Circuit Interrupter),
which is an extremely sensitive circuit breaker
that will help to protect against severe electrical
shock if a ground fault develops. If such a
condition occurs, the GFCI will break the circuit
by turning off the power to the protected outlets.
Should this occur, unplug all the appliances on
that circuit and press the reset button on the GFCI
equipped outlet.
If the GFCI keeps tripping, have the electrical
system checked and repaired, if necessary, before
using again.
AUXILIARY 110-VOLT
GENERATOR
110-Volt House Circuit Breakers
WARNING
The GFCI will not completely eliminate
electrical shock. Small children and
persons with heart conditions or other
disabilities which make them especially
sensitive to electrical shock may still be
injured by a 110-volt receptacles even
though protected by a Ground Fault
Circuit Interrupter.
WARNING
Careless handling
of the generator and
electrical components can be fatal.
Never
touch electrical leads or
appliances when your hands are wet, or
when standing in water or on wet ground.
Do not
attempt to repair the generator
yourself. Service should be performed by
an authorized service center.
Do not
plug the power cord into the
generator receptacle while the generator
is running.
Push to
Reset circuit
after monthly
testing or
ground fault
tripping.
Push to
Test at least
monthly.
Should break
circuit. Press
Reset button
to reconnect.
GFCI Outlet
(Ground Fault Protector)