4-9
SECTION 4 -
APPLIANCES AND SYSTEMS
Further Information
Please see the furnace operating instructions
provided in your InfoCase for further
information, including operating precautions,
and periodic maintenance. See the Coach
Maintenance Schedule for recommended
intervals.
NOTE: If the furnace burner has any residuals
of metal protectant or lubricants used
during manufacture of the furnace, it
may smoke slightly when the furnace is
used for the first time and may set off
your smoke alarm.
We recommend that you provide
adequate ventilation when using the
furnace for the first time to avoid a
nuisance smoke alarm.
We do not recommend removing the
smoke alarm battery.
DUCTED ROOF AIR
CONDITIONING SYSTEM
The furnace thermostat also controls ducted
roof air conditioner operation when the
thermostat switch is placed in “cool” position.
All cooling functions controlling to setpoint
have a short cycle protection time delay of 3
minutes. There will be no delay if the cycle OFF
time exceeds 3 minutes.
NOTE: The ducted roof air conditioning system
has ceiling registers that can be closed if
necessary to force more cool air toward
a specific area of the coach or to route
cool air away from a specific area. If too
many vents are closed, however, it can
cause the air conditioner unit to shut
down, particularly in high humidity
conditions.
Further Information
Refer to the air conditioner manufacturer’s
information in your InfoCase for complete
operating instructions.
ENERGY MANAGEMENT
SYSTEM (EMS)
–If Equipped
The Energy Management System (EMS)
monitors the electrical usage of the appliances
and equipment in the coach and allows you to use
certain high energy appliances, such as the
microwave or washer/dryer, without overloading
the shoreline circuit breaker to prevent nuisance
tripping.
Further Information
Please read the Energy Management System
Owners Guide in your InfoCase for important
information on how this system operates under
several conditions, whether 20-amp, 30-amp, and
50-amp connections, or generator service. In 50-
amp service, the load meter is blank. In all other
conditions, the load meter displays actual current
load.
REAR AIR CONDITIONER
POWER SELECTOR SWITCH
–If Equipped
(models with 2 roof air units and 30-amp
service only)
If you want to run the rear AC unit, you must
switch the Rear A/C Selector switch to the proper
power source.
EMS Display Panel
(Located on Monitor Panel)
-Typical View