Power
In
Aux Power
Out
J6
J5
1
2
3
4
J10
J8
J9
Relay Outputs
2
3
4
5
6
7
8
Aux
NO COM NC
NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC
VIEW OF CIRCUIT BOARD IN EA800 BASE CONSOLE
1
Wired Sensor Inputs
S
PECIFICATIONS
EA800 Console Input Voltage
11 to 26VDC @ ≤ 500mA current draw
Wireless Sensor Input Voltage
(EA-WMFS, EA-WTS, EA-WHS)
12VDC @ ≤ 100mA current draw via 2.1 mm barrel plug,
center positive
OR
2xAA Alkaline Batteries (1.5V Cell)
EA800 Console Auxiliary Output
Voltage
Equivalent to DC Input Voltage used: 11 to 26VDC.
(Maximum output current 0.5A).
Environmental Operating Range
(EA800, EA-WMFS, EA-WTS,
EA-WHS)
Temperature: 0°C to 50°C (32°F to 122°F). Not for
installation inside coolers or freezers.
Humidity: 5% to 95% RH, non-condensing.
Ambient Environmental Quality
Indoor use intended, non-corrosive environment.
Relay Contact Ratings
Max 30VDC @ 1 Amp, resistive
EA800 Real-Time Clock Battery
CR2032 (3V Cell)
Ethernet (EA800-ip only)
10/100BASE-TX/FX; fully compliant to IEEE 802.3u standard
Q
UICK
S
TART
G
UIDE
This guide provides basic setup instructions for the
EnviroAlert EA800 and EA800-ip Critical Condition
Monitoring System and associated sensors. Installers
should refer to the Installation Manual (found online
at www.winland.com) for complete instructions and
specifications, and to become familiar with the many
features provided by the EA800. The EA800 allows
connection of up to 4 wired and 4 wireless sensors.
To use the EA800-ip’s advanced features, set up an
account at www.ea800ip.com. Since the EA800-ip
utilizes a cloud computing architecture, no client
software is required.
R
EAD
THE
I
NSTALLATION
/O
WNER
’
S
M
ANUAL
FOR
COMPLETE
INSTRUCTIONS
.
Installation/Owner’s Manual can be found online at www.winland.com
• All power terminals must be connected to a Class 2 power limited circuit complying with
National Electrical Code NFPA 70, Article 725. Where required, this equipment is to be
isolated from the main supply by a limited power source as specified in EN60950.
• Batteries shall not cause explosion or produce a fire hazard as a result of excessive charge
or discharge.
• Ensure all wiring for wired sensor connections is done before powering on or
programming the EA800 console.
• If the equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
1950 Excel Drive • Mankato, MN 56001 USA
(Tech Support 8:00am - 5:00pm Central)
(800) 635-4269 • (507) 625-7231 P • (507) 387-2488 F
www.winland.com
I
NSTALLATION
O
VERVIEW
1. Installing Base Console
Do not connect or disconnect power, sensor, or alarm wiring
while power is applied. Connecting and disconnecting the
EA800 base console with power connected may damage the
base console or result in improper or unreliable operation.
Connection of unsuitable loads to this connection may
damage the power supply and EA800 base console, or result
in improper or unreliable operation.
Using a terminal block adapter, connect power supply
+
and
-
leads to
POWER IN
(
+
) and
(
-
) on
J5
. Observe proper polarity.
EA800 Input Voltage:
11 to 26VDC at ≤ 500mA
Note:
The input voltage specification does not include requirements for loads connected to
Aux Power Out.
If
Aux Power Out
is to be used, connect
+
and
-
leads to
AUX POWER OUT
(
+
) and (
-
) on
J5
using a terminal block adapter. When base console is powered, a 30-minute timer starts.
The console will alarm after this timer expires unless one or more sensors are installed.
D-011-0153 Rev F (02/2012)