Tab 11-8
Oil systems (XX2NNN, part 2)
Description
Usual oper-
ation (value
or range)
Safeguard setting
Medium / physical value / location
Signal number Func-
tion
Le-
vel
Trigger
value
De-
lay
Servo oil
Servo oil / flow / inlet each servo oil pump
-
FS2061-nnA
ALM
L
min
0
ALM
H
max
0
Servo oil leakage / flow / servo oil supply unit
-
LS2055A
ALM
H
max
10
Oil mist
Oil mist / concentration / crankcase (each
cylinder)
-
AE2401-nnA
ALM
H
max
0
AS2401-02A
ALM
H
max
0
-
AS2401S
SLD
H
max
60
Oil mist / concentration / gearcase
-
AE2415A
ALM
H
max
0
Oil mist / concentration / fuel supply unit
-
AE2421-22A
ALM
H
max
0
Piston cooling oil
Piston cooling oil / temperature [°C] / outlet
each cylinder
45 to 75
TE2501-nnA
ALM
H
≥
80
0
SLD
H
≥
85
60
Piston cooling oil / flow [l/min] / outlet each
cylinder
-
FS2521-nnS
SHD
L
min
15
1
The trigger values are only applicable above 30% engine load.
2
The concentration is related to the lower explosive level (LEL).
X92-B
AA00-0000-00AAA-033B-A
Operation Manual
List of usual values and safeguard settings
Winterthur Gas & Diesel Ltd.
- 425 -
Issue 002 2021-11
Содержание X92-B
Страница 8: ...X92 B Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 8 Issue 002 2021 11...
Страница 12: ...X92 B Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 12 Issue 002 2021 11...
Страница 113: ...X92 B Operation Manual Page left intentionally blank Winterthur Gas Diesel Ltd 113 Issue 002 2021 11...
Страница 241: ...7 Installation 7 1 Installation 242 X92 B Operation Manual Winterthur Gas Diesel Ltd 241 Issue 002 2021 11...