![Wine Guardian D0200 Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/wine-guardian/d0200/d0200_installation-operation-and-maintenance-manual_986042056.webp)
56
Advanced Troubleshooting
Evaporator coil is freezing
Possible Cause
Solution
Charge too low
Check sight glass
Check for leaks
Add refrigerant
TXV malfunctioning Repair or replace
High pressure switch keeps tripping
Even After Checking for Obstructions and Dirty Filters/Coils
Possible Cause
Solution
Condenser fan not operating Repair or replace
Defective switch Replace
Unit cycles on and off more than 8 times/hr
Possible Cause
Solution
Thermostat malfunctioning Check the thermostat guide for
thermostat information
Low suction pressure Check low pressure switch
Check pressure and adjust superheat
High pitched or loud rubbing noise, clanking or vibration
Possible Cause
Solution
Fans loose or malfunctioning Repair or replace
Excessive compressor vibration Replace
TXV malfunctioning Repair or replace
Replacing the blowers
NOTE: When replacing the fan or motor, replace the fan and motor as a unit.
Do not remove the motor from the impeller wheel.
IMPORTANT
This section is intended for qualified refrigeration service technicians only.
The technician should repeat all of the previous troubleshooting steps before taking action on these
more technical solutions.
Содержание D0200
Страница 12: ...12 Overview Illustration of the Wine Guardian Unit Fig 1 Fig 2...
Страница 13: ...13 Overview Illustration of water cooled system Fig 3 Fig 4...
Страница 14: ...14 Wiring diagrams D025 and D050 Fig 5...
Страница 15: ...15 Wiring diagram D088 and D200 Fig 6...
Страница 16: ...16 Wiring diagram water cooled D025 and D050 Fig 7...
Страница 17: ...17 Wiring diagram water cooled D088 and D200 Fig 8...