39
Troubleshooting
Before proceeding, read and understand the safety information contained in the
Safety Section of the Wine Guardian Manual
For in-depth Troubleshooting please head to
Resetting the High-Pressure Switch
1. Remove the access panel, grille, or duct collar on the condenser to gain access
to the High-Pressure Switch.
2. Locate the High-Pressure Switch near the compressor (Fig. 1).
3. Push the button until it locks into position.
4. Push the rocker switch to restart the unit.
High-Pressure Switch Has Shut Down the Unit
Every Wine Guardian unit has a manual reset high-pressure switch in the refrigeration
system. This switch shuts the compressor and condenser down if the head pressure
in the system is too high. It is intended to protect the compressor. Restricted airflow
through the condenser is the most common reason for the pressure to become too
high. This can be caused by dust covering the filter or an obstruction blocking the
airflow in the duct or grille.
Possible Cause
Solution
Head Pressure in unit is too high because
an obstruction is restricting airflow
Remove the obstruction in the duct/grille
or clean the filter. Then restart the unit
after resetting the high-pressure switch.
Содержание 99H0204-20
Страница 12: ...12 Overview of the Evaporator Fig 1...
Страница 14: ...14 Overview of the Condenser Fig 2...
Страница 15: ...15 Refrigeration Illustration Fig 3...
Страница 16: ...16 Wiring Diagram for SP25 Fig 4 DS025 Condenser...
Страница 18: ...18...
Страница 19: ...19 Specifications Wine Guardian Specification Sheet 60Hz models...