background image

 

windy

nation

 

 

 

Revision 1 

VertaMax User Manual

 

Page 13 of 15

 

 

5.2 T

ROUBLESHOOTING

 

Problem 

 

CAUSE 

Possible Remedies 

 

No Power, No 

Indicator 

Battery is defective 

Replace battery 

Blown fuses 

Open Fuse cover on inverter and check 

fuses for continuity. 

Loose cable connections  Check connections and tighten as 

necessary 

Unit operates for a 

short period and 

then turns off 

Load is trying to draw too 

much current 

Be sure load is less than rated watts of 

inverter. Remove excessive load. Turn 

inverter off and back on to reset. 

Alarm sounds. 

Low voltage 

 

Shorten battery cables or use thicker 

battery cables. Recharge battery.  

Over Temperature 

Protection 

Allow unit to cool. Improve air circulation 

around unit. Locate unit to a cooler 

environment. Reduce load if continuous 

operation is required 

Overload 

Reduce load or use a larger inverter 

Bad Connections 

Check all connections and tighten as 

needed. 

Measured inverter 

output voltage is 

too low. 

Sine waves may read 

incorrectly on typical 

multi-meters 

Inverter’s “pure sine wave” output requires 

“true RMS” voltmeter for accurate 

measurements 

Battery voltage is too low  Recharge battery 
Over load 

Reduce the load 

Battery run time is 

less than expected 

AC product’s power 

consumption is higher 

than rated 

Use a larger battery to make up for 

increased 

power requirement 

Battery is old or defective  Replace battery. 
Battery is not being 

properly charged 

Some chargers are not able to fully 

recharge a battery. Make sure you use a 

powerful charger. 

Power dissipation in DC 

cables. 

Use shorter/thicker DC cables. 

Television and/or 

stereo interference  Audio/Video interference. 

Reposition equipment antennas and 

Inverter. Position the power inverter and 

wiring as far as possible from electronic 

equipment, antenna and cables. 
Make sure the chassis ground connection 

on the inverter is solidly connected. 
Keep battery cables as short as possible 

and twist them together (2-3x per foot). 

5.3 S

UPPORT

 

If you are experiencing technical problems, and cannot find a solution in this manual, you can 

contact Windy Nation Inc. for further assistance. 

 

Call: (805) 323-6445 

 

Email: 

[email protected]

 

 

Write: 1404 Fleet Ave., Ventura, CA 93003 

For challenging issues or to just ask a question, consider using our FREE Community Forums! 

Consult our community of DIY'ers for fast answers to all your questions. 

 

Post on our Forums: 

http://forums.windynation.com/community/ 

Содержание VertaMax PIN-0500-12M

Страница 1: ...windynation VertaMax 500 Watt Power Inverter Series PIN 0500 12M Modified Sine Wave PIN 0500 12P Pure Sine Wave User s Manual...

Страница 2: ...2 2 Low Input Voltage 8 3 2 3 Power Overload 8 3 2 4 Over Heating 8 3 2 5 Short Circuit 9 3 2 6 Functional Matrix 9 3 2 1 Fuse Replacement 9 4 Application 9 4 1 Power Consumption 9 4 2 Typical Power C...

Страница 3: ...Inverter may be used for many different applications including Solar PV battery systems Wind Turbine battery systems Recreational Vehicles Boats etc Please read this manual carefully before installing...

Страница 4: ...use 1 3 SPECIFICATIONS 1 3 1 Electrical Specifications Parameter PIN 0500 12M PIN 0500 12P Continuous Rated Power 500 Watts Peak Surge Power 1000 Watts Input Voltage Nominal 12 13 VDC Input Voltage M...

Страница 5: ...using a copper wire to connect the grounding terminal on the VertaMax enclosure to earth ground or chassis ground The grounding terminal if applicable is located on the DC Input end of the inverter V...

Страница 6: ...stance connection For example if the power source is a battery the cable must be terminated with a battery terminal that clamps to the post on the battery IMPORTANT If there is an excessive voltage dr...

Страница 7: ...R The VertaMax features a Soft Start to handle the power surge that is created when some appliances are turned on This feature helps protect both the appliance and the inverter from excessive power dr...

Страница 8: ...is important to remove or shut down computers or other sensitive devices that may be connected to the VertaMax and recharge the battery before its capacity drops too low The inverter can operate while...

Страница 9: ...n No 12V DC input On Off Off Off 3 2 1 Fuse Replacement This inverter is equipped with two replaceable 30 amp internal fuses Never check or remove the fuses when the inverter is connected to a DC powe...

Страница 10: ...ulb 100 W 100 Blender 400 4 3 WIRE GAUGE REFERENCE 4 3 1 Ampacity Table Load Amperage Power 12VDC 10A 120W 20A 240W 30A 360W 40A 480W 50A 600W 60A 720W 70A 840W 80A 960W 100A 1200W 120A 1440W 160A 192...

Страница 11: ...e 100A h Battery Operating Time 100 watt 9 Amps 5 5 hours 11 hours 200 watt 19 Amps 2 6 hours 5 2 hours 500 watt 47 Amps 1 hour 2 hours All Values are approximate 4 4 2 Battery State of Charge SOC You...

Страница 12: ...ttery Amps Required Divide the total wattage required from step 1 above by the battery voltage 12 to determine the DC amps required STEP 3 Estimate Battery Amp Hours Required Multiply the DC amps requ...

Страница 13: ...oltage is too low Recharge battery Over load Reduce the load Battery run time is less than expected AC product s power consumption is higher than rated Use a larger battery to make up for increased po...

Страница 14: ...request within the Warranty Period by contacting Windy Nation in writing or via telephone and obtaining a Returned Materials Authorization RMA number This RMA must be obtained before returning any pro...

Страница 15: ...BY ANY PERSON 5 4 4 Limitation of Liability UNDER NO CIRCUMSTANCES WILL WINDY NATION OR ITS AFFILIATES OR SUPPLIERS BE LIABLE OR RESPONSIBLE FOR ANY LOSS OF USE INTERRUPTION OF BUSINESS LOST PROFITS...

Отзывы: