See previous examples for how to associate motor line with motor groups and motor groups with smoke
zones.
Master-Slave configuration:
In section 2
Press “Configuration”
“Smoke zone”
“5”
“arrow down”
“Slave 1 of this smoke zone”
Select “1” to select section ID 1
“1” again, to select smoke zone 1 on section 1
Smoke area 1 is now configured with Section 2, smoke zone 5 as a Master of Section 1 smoke zone 1.
4.2.3 Configuration of wind direction dependent smoke ventilation
We want all façade windows to open independent of the wind direction but the roof windows should only
open if the wind is not coming from the direction the windows are facing. Roof windows, facing north, must
close if the wind is from a northerly direction. Otherwise, they must open. In section 2, motor group 1 is
facing south and motor group 2 is facing north.
Press “Configuration”
“Motor group”
“1”
“arrow down”
“Wind direction where to close during
alarm”
Select “165°”, “180°” and “195°”
Pres
s “Configuration”
“Motor group”
“2”
“arrow down”
“Wind direction where to close during
alarm”
Select “345°”, “0°” and “15°”
4.2.4 Configuration of weather station sensors
All weather station sensors are connected to the WSC 540, section 2 in this example.
4.2.4.1 Configuration of the wind direction and wind speed sensors
Consult paragraph 10.2 in the WSC 5xx installation instructions for how to install the WOW 201, WOW 202
and WOW 204 wind sensors.
Press “Configuration”
“arrow down ”
“Weather station type”
Set “Sensor type” = “WOW”
4.2.4.2 Configuring the Input of the Rain signal
To propagate the Rain Safety signal, from one section of the WSC to another, the input of the signal is
associated with a smoke zone and a Master-Slave relation is used among all smoke zones, with motor lines
that we want to react, to this Safety signal. In this example, the Rain signal Input on section 2, is associated
with smoke zone 5. The signal will then be propagated to the motor lines associated with Section 1, smoke
zone 1.
The motor line S5.x2 in Section1, which is running the internal dampers, is configured not to react to the
Rain Safety signal.
In section 2
Press “Configuration”
“Local Input”
“S1.x2.1”
Set
“Control smoke zones” = “5”
Set “Function in controlled smoke zone” = “Comfort safety”
In section 1
Press “Configuration”
“Motor group”
“3” selecting the motor group associated with motor line S5.x2.
Set “Use ‘Safety’ from smoke zone” = “No”
The WSC 540 KIMM KMM0 is now configured and ready for use.