OPM-155/A

TROUBLESHOOTING TABLE

Problem

Possible Causes

Unit will not crank when power fails

Digital genset not in AUTO

Transfer control switch not in AUTOMATIC position

Incorrect wiring between ATS and genset

Defective control relay in ATS

Fuse(s) blown in the DSE 7310 MKII

Defective DSE 7310 MKII

Loose or dirty battery terminals

Defective starter

Defective start solenoid

Low/dead battery

Engine won’t crank

Low/dead battery

Blown DC fuses

Defective DSE 7310 MKII

Defective key switch

Loose or dirty battery terminals

Defective starter

Defective start solenoid

Locked up engine genset

Defective engine harness

Improper battery voltage to start solenoid, fuel pump, or fuel solenoid

Engine cranks but will not start

Improper fuel delivery to the unit

Fuel supply shut off

Fuel tank empty

Air in the fuel system

Engine fuel solenoid has not opened

Defective fuel pump

Defective fuel solenoid

Defective engine harness

Improper battery voltage to fuel pump or fuel solenoid

Engine starts, then stops and alarm light 

comes on

Engine oil pressure is low

Engine has high water temperature

Engine has overspeed

Engine has gone into overcrank

No output from AC generator

Loss of speed signal

Loss of run signal

Engine will not come up to speed after 

it starts

Insufficient fuel volume getting to the unit

  1. Too small of fuel line

    2. Fuel racks not open properly

  Governor is defective

  AC short in generator components

ATS will not transfer to Emergency 

Supply (generator)

No AC generator output

Defective ATS control board. See ATS 

 manual

Circuit breaker open or defective

ATS will not re-transfer to normal power Proper power line not available at line 

  terminals in ATS panel

Defective ATS control board. See ATS 

 manual

No AC output from generator

Defective diode

Defective voltage regulator

Defective rotor

Defective stator

Defective exciter rotor

Defective exciter stator

AC short in the output leads

Defective/open generator output breaker

Wiring error

Содержание DR450V4

Страница 1: ...r need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCH...

Страница 2: ...TER STORAGE BRINGING OUT OF STORAGE TROUBLESHOOTING TABLE 18 AVR WIRING 19 WIRING SIZE TABLE 20 DSE 7310 MKII WIRING DIAGRAM 22 AC WIRING 23 LIMITED WARRANTY 24 SAVE THESE INSTRUCTIONS This manual con...

Страница 3: ...ne generator set has been designed and manufactured to allow safe reliable performance Poor maintenance improper or careless use can result in potentially deadly hazards from electrical shock exhaust...

Страница 4: ...049 ohms per phase 22 C Exciter Stator Resistance 17 ohms 22 C Exciter Rotor Resistance 0 092 ohms per phase 22 C DR500V4 GENERATOR Standby Wattage 500 000 500 000 500 000 500 000 Volts 120 208 120 24...

Страница 5: ...phase 22 C Exciter Stator Resistance 17 ohms 22 C Exciter Rotor Resistance 0 092 ohms per phase 22 C DR600V4 GENERATOR Standby Wattage 600 000 600 000 600 000 600 000 Volts 120 208 120 240 277 480 34...

Страница 6: ...fore any generator is shipped from the factory it is fully checked for performance The generator is loaded to its full capacity and the voltage current and frequency are carefully checked Rated output...

Страница 7: ...ery hold down brackets hardware e Unit components or accessory items shipped loose for on site installation f Optional accessories 3 Remove main frame hold down bolts 4 Unit can now be lifted from shi...

Страница 8: ...INJURY PERSONAL INJURY Before proceeding with the installation be sure the DSE7310 is in the stop position Before proceeding with the installation be sure the Generator MLCB Main Line Circuit Breaker...

Страница 9: ...oil and keep the crankcase properly filled will cause excessive engine wear and shorten its useful life Winco recommends our 5W 40 fully synthetic heavy duty engine oil to give you maximum cold weath...

Страница 10: ...panel The ATS is then installed between the main panel and the emergency distribution panel Suggested circuits freezer refrigerator furnace emergency lights sump pump emergency outlet circuits etc To...

Страница 11: ...sed upon the long time Ir setting of the breakers For example if the Ir of the breaker is set at 200 and the Isd is set at 1 5 the short term breaker setting is 250 amps Instantaneous Protection The d...

Страница 12: ...n must be separate conduit You cannot mix AC and DC leads at the same conduit To install the wires reference the following picture Use a small flat head screwdriver to push the release spring inside t...

Страница 13: ...tdown alarms are latching The fault must be removed and the STOP RESET button pressed to reset the module The icon will be flashing in the display INITIAL START UP WARNING EQUIPMENT DAMAGE Before atte...

Страница 14: ...ds possibly damaging them NOTICE If for any reason during the check out procedure the voltage and frequency are not correct depress the STOP RESET button and correct the trouble before proceeding 4 St...

Страница 15: ...lowest points of the cooling water pipes 4 Close any taps and check that the spring loaded covers on the nipples close completely Install the rubber plugs and the filler cap s MAINTENANCE WARNING Befo...

Страница 16: ...es Top up as necessary Alternatively you can drain the coolant also drain the coolant filter 8 Drain any water and contamination from the fuel filters and fuel tank Fill the fuel tank completely to av...

Страница 17: ...4 Check the drive belt s 5 Check the condition of all rubber hoses and re tighten the hose clamps 6 Close the drain taps and install any drain plugs 7 Check the coolant level Top up as necessary 8 Co...

Страница 18: ...fective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water...

Страница 19: ...made to the voltage regulator VOLTS To adjust generator output voltage Clockwise to increase voltage STABILITY To prevent voltage hunting Clockwise to increase the dampaning effect STANDARD CONNECTIO...

Страница 20: ...N THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 202...

Страница 21: ...21 OPM 155 A THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 22: ...6723 67 57 67 57 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855...

Страница 23: ...EE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THRE...

Страница 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: