13

OPM-155/A

STARTING PROCEDURE

CONTROL LAYOUT

 

 

STOP/RESET - This button places the module 

into its Stop/Reset mode. This will clear any 

alarm conditions for which the triggering 

criteria have been removed. The fuel supply 

de-energizes and the engine comes to a 

standstill. Should a remote start signal be 

present while operating in this mode, a 

remote start WILL NOT occur.
MANUAL MODE - This button places the 

module into its Manual Mode. Once in 

Manual Mode, the model responds to the 

Start button to start the generator and run it 

off load.

START - Pressing this button from STOP/RESET 

will start the engine and run the load. 

AUTO MODE - This button places the 

module into its Auto Mode. This mode allows 

the module to control the function of the 

generator automatically. 
ALARM/LAMP TEST - This button silences the 

audible alarm in the controller, de-activates 

the Audible Alarm output (if configured) and 

illuminates all of the LEDs on the module’s 

face as a lamp test function.
MENU NAVIGATION - Used for navigating the 

instrumentation, event log, and configuration 

screens. 
A small rocker switch is located on the 

underside of the engine control cabinet.

On gaseous models, the engine timing is 

controlled by the ECU on the engine and you 

need to tell it what fuel you want to operate 

on; LP or NG.  

On diesel models, this switch has been 

disconnected and will do nothing.

PROTECTIONS

When an alarm is present, the common alarm LED if 

configures will illuminate. The LCD display will show an icon 

to indicate the failure.

WARNINGS

Warnings are non-critical alarm conditions and do not 

affect the operation of the generator system, they serve to 

draw the operator’s attention to an undesirable condition. 

Warning alarms are self-resetting when the fault condition 

is removed. The icon will appear steady in the display.

SHUTDOWN

Shutdowns are critical alarm conditions that stop the 

engine and draw the operator’s attention to an undesirable 

condition. Shutdown alarms are latching. The fault must be 

removed and the STOP/RESET button pressed to reset the 

module. The icon will be flashing in the display.

INITIAL START UP

WARNING: EQUIPMENT DAMAGE

Before attempting  to start this unit, complete the start-

up checklist and ensure the generator mainline circuit 

breaker is in the proper position prior to starting. 

Starting this unit without it properly connected can 

cause serious personal injury or equipment damage.

DO NOT jump start these engine-generator sets. Starting 

these units on a low battery or jump starting them will 

cause damage to the engine control module. 

Refer to the start-up checklist, WINCO form F-153, that was 

sent along with this manual. After completing the checklist, 

the engine-generator set is ready for initial start-up. 

MANUAL MODE

1. Press and release the Manual Mode button. The small 

LED light 

next to it should come on. 

Note:

 There is no start delay in this mode of operation.

2. Press and release the green Start Engine button. The 

DSE 7310 MKII will send two signals to the engine. The first 

signal wire #21 will engage the fuel solenoid, the second 

wire, #22, will engage the starter on the engine. At this 

point the DSE7310 will start the cranking cycle (10 seconds 

on and 10 seconds off).

Note: Wire #93 is energized to turn on the glow plugs for 

15 seconds first and then the starter and fuel solenoid are 

engaged.

If the engine fails to start during this cranking period, the 

starter motor is disengaged and goes into a rest mode after 

which a second attempt is made to start the engine. Should 

this sequence continue through 3 cranking cycles the start 

sequence will be stopped and the display will show ‘FAILED 

TO START”. 

3. During manual operation, the load will not normally be 

applied to the generator. But caution must be used, if the 

line power should fail or be turned off the transfer switch 

during manual operation the load may be applied to the 

generator.

With the engine running smoothly check the no load 

voltage and frequency on the digital display. The voltage 

should be 208/240/480 AC depending on which model 

you have and a frequency of 59.5 to 60.5 hertz (Hz). 

Содержание DR450V4

Страница 1: ...r need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCH...

Страница 2: ...TER STORAGE BRINGING OUT OF STORAGE TROUBLESHOOTING TABLE 18 AVR WIRING 19 WIRING SIZE TABLE 20 DSE 7310 MKII WIRING DIAGRAM 22 AC WIRING 23 LIMITED WARRANTY 24 SAVE THESE INSTRUCTIONS This manual con...

Страница 3: ...ne generator set has been designed and manufactured to allow safe reliable performance Poor maintenance improper or careless use can result in potentially deadly hazards from electrical shock exhaust...

Страница 4: ...049 ohms per phase 22 C Exciter Stator Resistance 17 ohms 22 C Exciter Rotor Resistance 0 092 ohms per phase 22 C DR500V4 GENERATOR Standby Wattage 500 000 500 000 500 000 500 000 Volts 120 208 120 24...

Страница 5: ...phase 22 C Exciter Stator Resistance 17 ohms 22 C Exciter Rotor Resistance 0 092 ohms per phase 22 C DR600V4 GENERATOR Standby Wattage 600 000 600 000 600 000 600 000 Volts 120 208 120 240 277 480 34...

Страница 6: ...fore any generator is shipped from the factory it is fully checked for performance The generator is loaded to its full capacity and the voltage current and frequency are carefully checked Rated output...

Страница 7: ...ery hold down brackets hardware e Unit components or accessory items shipped loose for on site installation f Optional accessories 3 Remove main frame hold down bolts 4 Unit can now be lifted from shi...

Страница 8: ...INJURY PERSONAL INJURY Before proceeding with the installation be sure the DSE7310 is in the stop position Before proceeding with the installation be sure the Generator MLCB Main Line Circuit Breaker...

Страница 9: ...oil and keep the crankcase properly filled will cause excessive engine wear and shorten its useful life Winco recommends our 5W 40 fully synthetic heavy duty engine oil to give you maximum cold weath...

Страница 10: ...panel The ATS is then installed between the main panel and the emergency distribution panel Suggested circuits freezer refrigerator furnace emergency lights sump pump emergency outlet circuits etc To...

Страница 11: ...sed upon the long time Ir setting of the breakers For example if the Ir of the breaker is set at 200 and the Isd is set at 1 5 the short term breaker setting is 250 amps Instantaneous Protection The d...

Страница 12: ...n must be separate conduit You cannot mix AC and DC leads at the same conduit To install the wires reference the following picture Use a small flat head screwdriver to push the release spring inside t...

Страница 13: ...tdown alarms are latching The fault must be removed and the STOP RESET button pressed to reset the module The icon will be flashing in the display INITIAL START UP WARNING EQUIPMENT DAMAGE Before atte...

Страница 14: ...ds possibly damaging them NOTICE If for any reason during the check out procedure the voltage and frequency are not correct depress the STOP RESET button and correct the trouble before proceeding 4 St...

Страница 15: ...lowest points of the cooling water pipes 4 Close any taps and check that the spring loaded covers on the nipples close completely Install the rubber plugs and the filler cap s MAINTENANCE WARNING Befo...

Страница 16: ...es Top up as necessary Alternatively you can drain the coolant also drain the coolant filter 8 Drain any water and contamination from the fuel filters and fuel tank Fill the fuel tank completely to av...

Страница 17: ...4 Check the drive belt s 5 Check the condition of all rubber hoses and re tighten the hose clamps 6 Close the drain taps and install any drain plugs 7 Check the coolant level Top up as necessary 8 Co...

Страница 18: ...fective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water...

Страница 19: ...made to the voltage regulator VOLTS To adjust generator output voltage Clockwise to increase voltage STABILITY To prevent voltage hunting Clockwise to increase the dampaning effect STANDARD CONNECTIO...

Страница 20: ...N THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 44 57 75 88 101 114 132 154 176 202...

Страница 21: ...21 OPM 155 A THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 22: ...6723 67 57 67 57 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855...

Страница 23: ...EE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THRE...

Страница 24: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Отзывы: