en
Faults, causes and remedies
94
WILO SE 2018-12
– The red fault signal LED
lights up
.
– The error code is shown on the display and stored in the fault memory.
– The contact is activated for the collective fault signal.
– If the internal buzzer is activated, there is an audible alarm signal.
▪ Pump fault
Status icon
of the respective pump
flashes
on the display.
11.3
Fault acknowledgement
Switch off the alarm by pressing the operating button. Acknowledge the fault via the
main menu or Easy Actions menu.
Main menu
1
5
3
2
Fig. 75:
Acknowledge fault
‡
All faults rectified.
1. Press the operating button for 3 s.
⇒ Menu 1.00 appears.
2. Turn the operating button until menu 6 appears.
3. Press the operating button.
⇒ Menu 6.01 appears.
4. Press the operating button.
5. Change value to “reset”: Turn the operating button.
6. Press the operating button.
▶ The fault indication is reset.
Easy Actions menu
‡
All faults rectified.
1. Starting the Easy Actions menu: Turn operating button 180°.
2. Select menu item “Err reset”.
3. Press the operating button.
▶ The fault indication is reset.
Fault acknowledgement failed
If there are further faults, the faults are displayed as follows:
▪ The fault LED lights up.
▪ The error code of the last fault is shown in the display.
All other faults can be called up from the fault memory.
If all faults have been rectified, acknowledge the faults again.
11.4
Fault memory
The switchgear stores the last ten faults in the fault memory. The fault memory works
according to the first in/first out principle. The faults are displayed in descending order
in the menu items 6.02 to 6.11:
▪ 6.02: the last/latest fault
▪ 6.11: the oldest fault
11.5
Error codes
Code
Fault
Cause
Remedy
E006
Rotating field error
Mains connection faulty, incorrect
rotating field
Establish a clockwise rotating field at the mains
connection.
In case of an alternating current
connection, deactivate rotating field monit-
oring!
E014.x
Leakage detection
The moisture probe of the connec-
ted pump was tripped.
See the installation and operating instructions
of the connected pump
E040
Fault, level sensor
No connection to the sensor
Check the connection cable and sensor, replace
the defective component.
Содержание Wilo-Control EC-L
Страница 2: ......
Страница 3: ...3 Deutsch 4 English 54 Fran ais 104 Polski 156 P 207 WILO187690...
Страница 209: ...ru Wilo Control EC L 209 1 1 1 1 2 1 3 1 4 www wilo com legal 2...
Страница 210: ...ru 210 WILO SE 2018 12 2 1 1 2 2...
Страница 211: ...ru Wilo Control EC L 211 2 3 2 4 2 5 IP 2 6 IP54 30 C 50 C 90 2 7 2 8 16 18 3...
Страница 216: ...ru 216 WILO SE 2018 12 1 2 3 4 5 6 6 4 3 IPS 6 4 4 Extern OFF 6 4 5 6 4 6 3 01 Extern OFF...
Страница 221: ...ru Wilo Control EC L 221 6 5 5 x Fig 9 30 1 1 2 2 3 3 6 5 6 off 1 2 on 1 on 2 Fig 10 off 1 2 on 1 1 on 2 2...
Страница 223: ...ru Wilo Control EC L 223 6 5 8 Fig 14 Fig 15 6 5 9 Fig 16...
Страница 225: ...ru Wilo Control EC L 225 Fig 19 SBM 250 1 A 6 5 13 SSM Fig 20 SSM 250 1 A 6 5 14 EBM...
Страница 228: ...ru 228 WILO SE 2018 12 7 7 1 1 2 SSM ESM SSM 7 1 1 1 2 1 Extern OFF 2 3 7 1 2 7 1 3 Extern OFF 3 01 3 04...
Страница 229: ...ru Wilo Control EC L 229 Extern OFF 7 1 4 7 2 3 01 OFF drain fill 7 2 1 4 3 1 2 5 Fig 24 1 1 2 2 3 1 2 4 5 1 2 1 2...
Страница 233: ...ru Wilo Control EC L 233 8 3 8 4 E006 5 68 off E080 x 5 69 off 6 01...
Страница 247: ...ru Wilo Control EC L 247 7 OFF 8 9 4 1 2 3 4 5 6 10 10 1 10...
Страница 248: ...ru 248 WILO SE 2018 12 10 2 1 10 3 Fig 72 SER Fig 73 7 01 on 1 3 1 00 2 7 3 7 01 4 7 07 5 6 0 0 25 0 5 1 2 7...
Страница 249: ...ru Wilo Control EC L 249 Fig 74 SER 7 01 on 1 3 1 00 2 7 3 7 01 4 7 08 5 6 on 7 11 11 1 11 2 11 3 Easy Actions...
Страница 252: ...ru 252 WILO SE 2018 12 www wilo recycling com 13 13 1 13 1 1 1 2 0 13 1 2 Ex i 13 1 3...
Страница 253: ...ru Wilo Control EC L 253 13 1 4 x Fig 76 217 4b 13 1 5 Fig 77 217 4b 13 1 6 1 3 1 00 2 5 3 5 01 4 5 64 5 6 on 7...
Страница 260: ......
Страница 261: ......
Страница 262: ......