13
Factory settings
For the factory settings, see Tab. 12 below.
Tab. 12: Factory settings
Menu
no.
Designation
Factory-configured values
1.0.0.0 Setpoints
• Controller:
approx. 60% of n
max
pump
•
Δ
p-c:
approx. 50% of H
max
pump
•
Δ
p-v:
approx. 50% of H
max
pump
2.0.0.0 Control mode
Δ
p-c activated
3.0.0.0
Δ
p-v gradient
Lowest value
2.3.3.0 Pump
ON
4.3.1.0 Base-load pump
MA
5.1.1.0 Operating mode
Main/standby mode
5.1.3.2 Internal/external pump
cycling
Internal
5.1.3.3 Pump cycling time interval
24 h
5.1.4.0 Pump enabled/disabled
Enabled
5.1.5.0 SSM
Collective fault signal
5.1.6.0 SBM
Collective run signal
5.1.7.0 External off
Collective external off
5.3.2.0 In1 (value range)
0–10 V active
5.4.1.0 In2 active/inactive
OFF
5.4.2.0 In2 (value range)
0-10 V
5.5.0.0 PID parameter
See chapter 9.4 “Setting the con-
trol mode” on page 95
5.6.1.0 HV/AC
HV
5.6.2.0 Emergency operation speed
approx. 60% of n
max
pump
5.6.3.0 Auto reset time
300 s
5.7.1.0 Display orientation
Display on original orientation
5.7.2.0 Pressure value correction
Active
5.7.6.0 SBM function
SBM: Run signal
5.8.1.1 Pump kick active/inactive
ON
5.8.1.2 Pump kick interval
24 h
5.8.1.3 Pump kick speed
n
min