7.4.6 Exhaust air for combustion and cooling diesel 

engine 
(Fig.  8) (Fig. 9a – 9b & variant) 

If the system is assembled with a pump driven by 
a diesel engine, the combustion gases of the 
engine must be evacuated outside by a pipe sup-
plied with an adequate silencer.
Back pressure cannot exceed recommendations 
for the type of diesel engine installed. The exhaust 
pipe must have an adequate size relative to the 
length of piping. It must be isolated and supplied 
with sufficient protections against accidental 
contacts with surfaces at high temperatures. 

Exhaust tailpipe cannot be close to windows or 
doors. Besides, exhaust gas must not come again 
in the pump room. 
Exhaust tailpipe must be protected from weather 
and must not allow the introduction of rainwater 
into the exhaust pipe or return of condensates 
back to the engine.
Hoses have to be as short as possible (ideally no 
longer than 5.0 m), with the fewest possible 
curves and a radius less than 2, 5 times the pipe 
diameter. 
Pipes must be supported, and a condensate drain 
system must be supplied with a material resistant 
to the acidity of the condensate.

The ventilation system in a pump room with diesel 
pumps with air cooling or air/water exchanger is 
crucial. This determines the correct functioning of 
the fire system.
The ventilation system must allow dissipation of 
heat produced during operation of the diesel 
pump system and ensure a correct air flow to cool 
the engine.
The room’s openings must consider the air flow 
necessary for the engine, which may vary accord-
ing to altitude. (See manufacturers’ data of diesel 
engine).

8 Commissioning

For the first commissioning, we advise you to hire 
the closest Wilo after-sales service agent or to 
contact our after-sales call centre.
Commissioning of the booster must be performed 
by qualified people.

8.1 General preparations and check

• Before switching on for the first time, check that 

the wiring has been done correctly, particularly 
the earth connection.

• To make sure that rigid connections are not asso-

ciated to mechanical stress.

• Fill the installation and during visual inspection, 

search the possible faults.

• Open gate valves on pump sides and on the dis-

charge pipe. 

CAUTION! Risk of product damages!
Never make the system running dry. The dry 
running destroys the pump mechanical seal 
tightness.

• The jockey pump tank is empty of water; inflate 

it to a 0.5 bar lower pressure than the pressure 
allowing the start of the jockey pump.

• Don’t exceed the maximum inflation value for 

the vessel.

CAUTION! Risk of product damages!
Tighten all the supply terminals before the com-
missioning of the booster!

If during installation it is necessary to conduct 
tests, make sure the pumps are properly filled with 
water before switching them on.
Before filling the pump unit with water, check the 
tightness of components, which could be loos-
ened during transport and handling.
Do not let the booster in automatic mode before 
the fire extinguishing system is completed 
assembled according to the standard; the com-
missioning of an incomplete fire extinguishing 
system rules out the warranty.

Procedure for commissioning

• During the pumping system automatic mode set-

ting, maintenance program procedures and 
responsibility of operation in case of accidental 
starting must be defined.

• For models with diesel engine, before operating, 

check the correct filling of batteries.

• For inspection of batteries, follow instructions 

given by manufacturer.

• Keep batteries away from flames and sparkles. For 

safety reasons do not lean above the batteries in 
operating and during installation or removal.

• Check the correct level of fuel in tanks of diesel 

engines and possibly add some fuel when engines 
are cold.

• Be careful to not spill fuel on motors, on rubber or 

plastic materials of the system.

• DO NOT add fuel when the engines are warm.

Содержание SiFire

Страница 1: ...re EN Pioneering for You 4 188 030 Ed 01 2013 11 Wilo de Einbau und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service nl Inbouw en bedieningsvoors...

Страница 2: ...Fig 1 Fig 2a A 2 2 E B C D...

Страница 3: ...Fig 2b Fig 3 21 25 26 13 11 12 19 15 22 27 20 24 23 2 1 14 4 16 7 5 6 10 18 17 9 9 10 8 3...

Страница 4: ...Fig 4 Fig 5...

Страница 5: ...Fig 6a 3 5 D D 4 D 2 3 C min max 1 8 m s Fig 6b min 3 5 D D 4 D max 2 m 2 3 C max 1 8 m s...

Страница 6: ...Fig 7 Fig 8 max 3 2 m min A B C D 2 4 5 6 3 8 7 1...

Страница 7: ...Fig 9a Fig 9b A B C D 800 800 800...

Страница 8: ...Fig 1a Fig 9a variant Fig 9b variant A B C D 800 800 800...

Страница 9: ...Fig 10 Fig 11 1 2 1 2 1...

Страница 10: ......

Страница 11: ...de Einbau und Betriebsanleitung 5 en Installation and operating instructions 29 fr Notice de montage et de mise en service 51 nl Inbouw en bedieningsvoorschriften 75...

Страница 12: ...sel pump 16 Connection for priming circuit of main pump 17 Main pump 18 Jockey pump 19 Tank for fuel leakages 20 Fuel tank vent valve 21 Fuel level gauge 22 Drain for cleaning of deposit in fuel tank...

Страница 13: ...ructions Wilo SiFire System 27 Fig 9a Variant Exhaust air for combustion and cooling diesel engine Fig 9b A Muffler B Exhaust thermal protection C Condensation drain D Expansion joint Fig 10 Automatic...

Страница 14: ...7 Installation and electrical connection 34 7 1 Installation 34 7 2 Safety recommendations 34 7 3 Control and environment 35 7 4 Electrical connection 35 7 4 1 General 35 7 4 2 Hydraulic connection 36...

Страница 15: ...t be adhered to but also the special safety instructions with danger symbols included under the following main points 2 1 Danger symbols used in this operating instruction Symbols General danger symbo...

Страница 16: ...l installation and maintenance work iscarried out by authorised and qualified personnel who are sufficiently informed from their own detailed study of the operating instructions Work on the product un...

Страница 17: ...eproof and ventilated enough with necessary spaces around pumps for movements and regular main tenance Theroommust beinaccordancewiththe EN 12845 standards Airflow for ventilation and for cooling of e...

Страница 18: ...requirements trans port handling difficulties particular perform ances etc using the main components described below main normalised back pull out pumps coupled to an electrical motor or diesel engin...

Страница 19: ...tion class IP 54 6 3 Function of the product The operational logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for pump starting The jockey pump of pre...

Страница 20: ...void access to the system for unauthorised persons The booster is a fire equipment using AUTO MATIC START and MANUAL STOP ONLY For this reason there must have a clearly visible sign in the system room...

Страница 21: ...ous tic and vibration levels In order not to transmit tension to the frame get the defects of alignment between theanchorsandthesupport surfacewith metal shims as shown in the figure 4 CAUTION Risk of...

Страница 22: ...following points are checked pipes are positioned in such a way as to avoid air accumulation suction pipes between the intake point and the pumping has to be as shortest as possible Its diameter must...

Страница 23: ...be performed by qualified people 8 1 General preparations and check Before switching on for the first time check that the wiring has been done correctly particularly the earth connection To make sure...

Страница 24: ...and electrical connections indicated in this manual are cor rectly done Make sure the valves at the suction and discharge side of the pump are open Make sure the pump is primed and filled with water C...

Страница 25: ...gas in the pump room Leakage on mechanical seal Vibrations noise and excessive temperatures could be due to misalignment of motor pump coupling 8 4 3 Commissioning jockey pump Manual Start Follow com...

Страница 26: ...o start the electric pump through the float signal Then follow pump box instructions to check the correct functioning of automatism Pump with diesel engine Before testing make sure that the return cir...

Страница 27: ...iesel engine it is advisable to disconnect the positive terminal of battery to prevent undesired start ups DANGER Risk of fatal injury Before changing the engine oil make sure the temperature is below...

Страница 28: ...ssure on diesel pump and the cooling circuit water flow CAUTION Risk of malfunction of the pump Always top up fuel and other fluids after per forming the tests 9 3 Test of automatic start of diesel pu...

Страница 29: ...hen origi nal spare parts are replaced by other parts with different characteristics 9 5 Residual risks during facility management WARNING Risk of cut Sharp edges orany not protected threaded parts en...

Страница 30: ...h Pump in cavita tion Review calculations to suit pump NPSHr Wrong diameter of the suction pipe and valves Pump in cavitation Review calculations to suit pump NPSHr Air inlet in the suction line Make...

Страница 31: ...ck and tighten Sliding between fan and motor and between coupling and coupling cover cap etc Guarantee the correct distance and re assemble Foreign parts in motor or pump Dismantle and remove Not alig...

Страница 32: ...re Unusual heating too high water oil temperature Pump overload frictions Dismantle and check Coupling out of axis Align correctly Ambient temperature higher than 40 C Ventilate the space Insufficient...

Страница 33: ...perations andhandling thefollowingmaterialsmustbesent to centres specialised in the collection and removal of waste Electromechanical and electronic components Electric cables Batteries Strainers Oil...

Страница 34: ......

Страница 35: ......

Страница 36: ...omagnetycznej 2004 108 WE 2004 108 EG pou it harmoniza n normy zejm na stosowanymi normami zharmonizowanymi a w szczeg lno ci viz p edchoz strana patrz poprzednia strona EL TR RO 3 5 7 5 99 CE Uygunlu...

Страница 37: ...20 27442100 Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 Ireland WILO Ireland T 353 61 227566 Italy Borromeo Milano T 39 25538351 Kazakhstan WILO Central Asia 050002 Almaty T 7...

Страница 38: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: