7.4.2 Hydraulic connection

Connect the following circuits to pumping tank or 
to priming tanks, by respecting the requirements 
imposed by standard:

• Flow rate metering circuit for the pump test. If the 

return to the tank is not possible, plan draining 
towards the mains drainage (see fig. 5). 

• Recirculation pipes. The recirculation circuit is 

used to prevent overheating and damage to 
pumps that remain in operation when the level of 
pressure in the system is reached and before they 
are turned off manually by authorised personnel.

• Sprinkler supply circuit of the fire extinguishing 

system room.

• Connect main pumps and jockey pump to the fire 

extinguishing system in accordance with the EN 
12845 standard and with installation diagram.

• Connect the jockey pump directly to the water 

tank by using a suction pipe which is adequately 
proportioned to avoid priming pump troubles.

• Check the tank of the jockey pump pre-inflation 

and adjust it according to the value of pressure 
which has to be maintained in the system accord-
ing to the instructions written on the tank or in its 
instruction manual.

7.4.3 Protection of the system

• The specific standard for fire extinguishing sys-

tems includes protections against short-circuits 
with the use of high breaking capacity fuses, 
which allow the passage of initial current for elec-
tric motors start-up for a period longer than 20 
seconds. These fuses are held inside the electric 
pump control panels. No thermal protections for 
the main fire extinguishing pumps are provided.

• Thermal protection against overload of jockey 

pump is installed inside its control box. It must be 
calibrated at a value slightly higher than the 
absorbed or nominal current (in) for the motor.

• Standard does not envisage protection against 

lack of water of pumps. In case of emergency, 
pumps must use all the available water of tanks to 
extinguish fire. 

• If diesel engines are present, the diesel engine 

electronic control panel manages engine operat-
ing parameters and possible alarms. For more 
information concerning diesel engine boxes, see 
the specialised instruction manual of the control 
panel.

Advise for installation

• According to the type of installation planned by 

the project, the booster can correctly operate if 
these following points are checked: 
• pipes are positioned in such a way as to avoid air 

accumulation.

• suction pipes between the intake point and the 

pumping has to be as shortest as possible. Its 
diameter must be suitable and equal or exceed 
the minimum required to maintain the maximum 
speed as indicated by the EN 12845 standard 

• pipes do not have leakages or air infiltration 

CAUTION! Risk of malfunction of the pump!
Valves or gate valves must not be directly 
installed on the pump suction.

• Include an eccentric cone as indicated by the EN 

12845 standard

7.4.4 Unit with positive head

[Fig. 6a - 6b]  (As defined in EN 12845, point 
10.6.2.2)

• Check the minimum level given for the storage 

tanks or the minimum historical level for virtually 
inexhaustible tanks in order to agree the condi-
tions for installation of the unit.

• Ensure that the diameter of the suction pipes is 

not less than DN 65, and check if the maximum 
suction speed does not exceed more than 1.8 m/s.

• Check if the NPSH available on the suction side of 

the pump is at least 1 meter higher than the NPSH 
required for flow rate and at the max water tem-
perature.

• Fit a strainer outside the water tank on the suction 

pipes, having a diameter measuring at least 1.5 
the nominal diameter of the pipe, and that does 
not allow the passage of parts bigger than 5mm in 
diameter.

• Install a gate valve between the strainer and the 

water tank.

7.4.5 Unit with suction lift

[Fig. 7] (as defined in EN 12845, point 10.6.2.3)

• Check the minimum level given for storage tanks, 

or the minimum historical level for virtually inex-
haustible tanks.

• Ensure a diameter of the suction pipes equal or 

higher than DN 80, and check if the max suction 
speed does not exceed 1.5 m/s.

• Check if NPSH available on the suction side of the 

pump is at least 1 meter higher than the NPSH 
required for flow rate and at the max water tem-
perature.

• Include independent intake pipes for the pumps 

equipped at the lowest point of the bottom valve.

• Fit a strainer on the suction pipes, before the bot-

tom valve. This strainer must be set up so that it 
can be cleaned without having to empty the tank. 
It must have a diameter measuring at least 1.5 the 
nominal diameter of the pipe and does not allow 
the passage of parts bigger than 5 mm in diame-
ter.

•  The distance between the rotation axis of the 

pump and the minimum water level must not 
exceed 3.2 meters.

•  Each pump must have automatic priming devices 

in compliance with the requirements of EN 12845, 
point 10.6.2.4.

Содержание SiFire

Страница 1: ...re EN Pioneering for You 4 188 030 Ed 01 2013 11 Wilo de Einbau und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service nl Inbouw en bedieningsvoors...

Страница 2: ...Fig 1 Fig 2a A 2 2 E B C D...

Страница 3: ...Fig 2b Fig 3 21 25 26 13 11 12 19 15 22 27 20 24 23 2 1 14 4 16 7 5 6 10 18 17 9 9 10 8 3...

Страница 4: ...Fig 4 Fig 5...

Страница 5: ...Fig 6a 3 5 D D 4 D 2 3 C min max 1 8 m s Fig 6b min 3 5 D D 4 D max 2 m 2 3 C max 1 8 m s...

Страница 6: ...Fig 7 Fig 8 max 3 2 m min A B C D 2 4 5 6 3 8 7 1...

Страница 7: ...Fig 9a Fig 9b A B C D 800 800 800...

Страница 8: ...Fig 1a Fig 9a variant Fig 9b variant A B C D 800 800 800...

Страница 9: ...Fig 10 Fig 11 1 2 1 2 1...

Страница 10: ......

Страница 11: ...de Einbau und Betriebsanleitung 5 en Installation and operating instructions 29 fr Notice de montage et de mise en service 51 nl Inbouw en bedieningsvoorschriften 75...

Страница 12: ...sel pump 16 Connection for priming circuit of main pump 17 Main pump 18 Jockey pump 19 Tank for fuel leakages 20 Fuel tank vent valve 21 Fuel level gauge 22 Drain for cleaning of deposit in fuel tank...

Страница 13: ...ructions Wilo SiFire System 27 Fig 9a Variant Exhaust air for combustion and cooling diesel engine Fig 9b A Muffler B Exhaust thermal protection C Condensation drain D Expansion joint Fig 10 Automatic...

Страница 14: ...7 Installation and electrical connection 34 7 1 Installation 34 7 2 Safety recommendations 34 7 3 Control and environment 35 7 4 Electrical connection 35 7 4 1 General 35 7 4 2 Hydraulic connection 36...

Страница 15: ...t be adhered to but also the special safety instructions with danger symbols included under the following main points 2 1 Danger symbols used in this operating instruction Symbols General danger symbo...

Страница 16: ...l installation and maintenance work iscarried out by authorised and qualified personnel who are sufficiently informed from their own detailed study of the operating instructions Work on the product un...

Страница 17: ...eproof and ventilated enough with necessary spaces around pumps for movements and regular main tenance Theroommust beinaccordancewiththe EN 12845 standards Airflow for ventilation and for cooling of e...

Страница 18: ...requirements trans port handling difficulties particular perform ances etc using the main components described below main normalised back pull out pumps coupled to an electrical motor or diesel engin...

Страница 19: ...tion class IP 54 6 3 Function of the product The operational logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for pump starting The jockey pump of pre...

Страница 20: ...void access to the system for unauthorised persons The booster is a fire equipment using AUTO MATIC START and MANUAL STOP ONLY For this reason there must have a clearly visible sign in the system room...

Страница 21: ...ous tic and vibration levels In order not to transmit tension to the frame get the defects of alignment between theanchorsandthesupport surfacewith metal shims as shown in the figure 4 CAUTION Risk of...

Страница 22: ...following points are checked pipes are positioned in such a way as to avoid air accumulation suction pipes between the intake point and the pumping has to be as shortest as possible Its diameter must...

Страница 23: ...be performed by qualified people 8 1 General preparations and check Before switching on for the first time check that the wiring has been done correctly particularly the earth connection To make sure...

Страница 24: ...and electrical connections indicated in this manual are cor rectly done Make sure the valves at the suction and discharge side of the pump are open Make sure the pump is primed and filled with water C...

Страница 25: ...gas in the pump room Leakage on mechanical seal Vibrations noise and excessive temperatures could be due to misalignment of motor pump coupling 8 4 3 Commissioning jockey pump Manual Start Follow com...

Страница 26: ...o start the electric pump through the float signal Then follow pump box instructions to check the correct functioning of automatism Pump with diesel engine Before testing make sure that the return cir...

Страница 27: ...iesel engine it is advisable to disconnect the positive terminal of battery to prevent undesired start ups DANGER Risk of fatal injury Before changing the engine oil make sure the temperature is below...

Страница 28: ...ssure on diesel pump and the cooling circuit water flow CAUTION Risk of malfunction of the pump Always top up fuel and other fluids after per forming the tests 9 3 Test of automatic start of diesel pu...

Страница 29: ...hen origi nal spare parts are replaced by other parts with different characteristics 9 5 Residual risks during facility management WARNING Risk of cut Sharp edges orany not protected threaded parts en...

Страница 30: ...h Pump in cavita tion Review calculations to suit pump NPSHr Wrong diameter of the suction pipe and valves Pump in cavitation Review calculations to suit pump NPSHr Air inlet in the suction line Make...

Страница 31: ...ck and tighten Sliding between fan and motor and between coupling and coupling cover cap etc Guarantee the correct distance and re assemble Foreign parts in motor or pump Dismantle and remove Not alig...

Страница 32: ...re Unusual heating too high water oil temperature Pump overload frictions Dismantle and check Coupling out of axis Align correctly Ambient temperature higher than 40 C Ventilate the space Insufficient...

Страница 33: ...perations andhandling thefollowingmaterialsmustbesent to centres specialised in the collection and removal of waste Electromechanical and electronic components Electric cables Batteries Strainers Oil...

Страница 34: ......

Страница 35: ......

Страница 36: ...omagnetycznej 2004 108 WE 2004 108 EG pou it harmoniza n normy zejm na stosowanymi normami zharmonizowanymi a w szczeg lno ci viz p edchoz strana patrz poprzednia strona EL TR RO 3 5 7 5 99 CE Uygunlu...

Страница 37: ...20 27442100 Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 Ireland WILO Ireland T 353 61 227566 Italy Borromeo Milano T 39 25538351 Kazakhstan WILO Central Asia 050002 Almaty T 7...

Страница 38: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: