Installation and operating instructions • Drive for Wilo-Helix2.0-VE / Wilo-Medana CH3-LE • Ed.01/2022-06
Additional settings
Ramp times
Remote configuration access
Automatic PWM
frequency reduction
Function pump kick, ramp times, remote configuration and automatic PWM frequency are
made:
Under "Settings"
1.
"Additional settings"
15.1
Pump kick
In order to prevent blocking of the pump, a pump kick is set on the pump. After a set time
interval, the pump starts and switches off after a short time. Prerequisite:
For the pump kick function, the mains voltage must not be interrupted.
CAUTION
Blockage of the pump due to long downtimes!
Long downtimes may lead to blockage of the pump. Do not deactivate
pump kick!
NOTICE
Via remote control, bus command, external control input OFF or 0 ... 10 V
signal of pumps that are switched off will start briefly. This prevents
blockage after long downtimes.
Pump kick
Pump kick: ON/OFF
Pump kick: Interval
Pump kick: Speed
Fig. 29: Pump kick setting
In the "Settings" menu , select:
Universal
Display text
1.6
Additional settings
1.6.1
Pump kick
1.6.1.1
Pump kick: ON/OFF
1.6.1.2
Pump kick: interval
1.6.1.3
Pump kick: speed
1.
"Additional settings"
2.
"Pump kick"
•
The pump kick can be switched on and off.
•
The time interval for the pump kick can be set between 2 and 72 hours. (Factory setting:
24 hours).
•
The pump speed at which the pump kick is performed can be set.
NOTICE
When it is planned to switch off the mains voltage for a longer period of
time, the pump kick must be performed using an external control by
switching on the mains voltage briefly. For this purpose, the pump must be
switched on by the controller before the power supply is interrupted.
15.2
Setting pump ramp times
In the "Settings" menu