Installation

Connect condensate drain

6.

If desired, a condensate drain can be connected. 
(1) Condensate drain for vertical installation position of the 
motor
(2) Condensate drain for horizontal motor installation 
position (only available in some models)

7.

Seal up unused condensate drain.

6.2 Electrical connection

Electrical connection

1.

Connect the connecting cable with power switched off and 
secure against reconnection.

2.

Lay the connecting cable such that it doesn't come into 
contact with the pump, the pump housing or the piping.

3.

Check whether the voltage and amperage in the mains match 
the specifications on the type plate of the pump.

4.

Open the terminal box.

5.

Lay the cable such that no condensation or spray water can 
run into the cable screws (Fig. A).

6.

Connect grounding cable.

1

2

Caution: Damage due to overheating!

For insulated piping systems, only the pump volute may be 
insulated, not the lantern and the motor. These could be 
damaged by heat build-up.

Danger: life threatening due to electrical shock!

Touching live parts can be fatal. Work on the electrical connec-
tion may only be performed by a trained electrician. Prior to 
connecting, ensure that the connecting line is voltage-free.

Warning: Danger due to a damaged cable!

For pumps that pump hot liquids or that are used in proximity to 
hot surfaces with temperatures above 194 °F [90 °C], a heat-
resistant cable must be used.

Note: 

For the correct cable size, refer to local wiring 

restrictions.

Caution: Damage due to incorrect voltage!

Never operate the pump with incorrect voltage. This could 
damage the motor.

A

B

Содержание Cronoline

Страница 1: ...Installation and operating instructions Wilo Cronoline 2 069 148 Ed 02 2007 05 11 Kothes...

Страница 2: ...e page 8 Installation page 8 Maintenance and Repair page 13 Screw torques page 18 Technical data page 5 Electrical connection page 10 Mechanical Installation page 8 Ventilate page 12 Check direction o...

Страница 3: ...Mechanical Seal Air Vent 4 Shaft 5 Lantern 6 Coupling guard 7 Coupling 8 Motor 9 Motor bolt 10 Condensate drain connection only in some models 11 Condensate drain connection 12 Volute Bolt 13 Suction...

Страница 4: ...Safety sticker Safety stickers are located on the motor giving important instructions on how to handle the pump The instructions on the safety sticker must be strictly obeyed Qualifications The pump...

Страница 5: ...r and secure against reconnection Never switch on the motor when the pump housing is open or the coupling guard is missing Never operate the pump without the coupling guard High Deadweight The pump ha...

Страница 6: ...rom 4 F to 250 F 20 C to 120 C Max permissible liquid temper ature range with high tempera ture seal at 175 psi 12 bar from 4 F to 250 F 20 C to 120 C at 165 psi 11 bar from 4 F to 285 F 20 C to 140 C...

Страница 7: ...is driven by an electric motor according to the NEMA standard Assembly For pumps up to an output of 20 HP the flanges are designed such that the pump can be mounted without additional support For pum...

Страница 8: ...6 Installation 6 1 Mechanical Installation Caution Damage due to incorrect packaging If the pump needs to be transported again at a later date it must be securely packaged for transit Use the origina...

Страница 9: ...ards Fig C In the case of installation with horizontal motor B the air vent valve must point upwards 3 If necessary disassemble the motor and rotate Page 14 The electrical terminal box may not point d...

Страница 10: ...the cable such that no condensation or spray water can run into the cable screws Fig A 6 Connect grounding cable 1 2 Caution Damage due to overheating For insulated piping systems only the pump volut...

Страница 11: ...ion when connecting to an automatic pump control device Comply with respective installation and operating instructions when wiring to automatic pump control device DDC or Building Management Systems B...

Страница 12: ...w on the motor run the pump note pres sure reverse rotation and recheck pressure The rotation that produces a higher pressure is the correct rotation for clarifi cation contact WILO 7 Turn on the pump...

Страница 13: ...to electrical shock Touching live components can be fatal Only qualified electri cians may work on the electrical system Prior to any mainte nance work disconnect the pump from the power supply and se...

Страница 14: ...ate drain 5 If motor is in horizontal installation position support the motor or secure it from falling with a crane and a suitable hoist 6 Remove screws 1 and remove coupling guard 2 on both sides 7...

Страница 15: ...keoutlanternunit 2 withcoupling shaft mechanicalseal and impeller using suitable lifting equipment and remove from pump housing Remove impeller 14 Loosen impeller fastening nut 1 counter clockwise 15...

Страница 16: ...s a lubricant 7 Insert a new O ring 2 in lantern groove 8 Carefully insert pre assembled unit consisting of coupling and shaft 2 into lantern 1 9 Hold coupling and shaft in place 2 in lantern 10 Press...

Страница 17: ...ighten coupling screws slightly at first until half coupling shells are lying on spacer disks 24 Then screw coupling together equally Torque Page 18 Specified distance of 0 197 inches 5 mm between lan...

Страница 18: ...Shaft Stainless steel 3 8 22 30 1 2 44 60 5 8 74 100 Pump housing lantern SAE Grade 5 5 8 75 100 Adapter flange lantern SAE Grade 5 5 16 18 25 1 2 44 60 Lantern motor SAE Grade 5 3 8 26 35 1 2 44 60 5...

Страница 19: ...an cover for dirt dust accumulation and clean if necessary Check ambient temperature and if neces sary ensure an ambient temperature 105 F 40 C by forced ventilation Pump runs at reduced capacity Inco...

Страница 20: ...LC 1290 North 25th Ave Melrose Park IL 60160 USA Phone 866 945 6872 WILO USA FAX 403 277 9456 Wilo Canada Inc Bay 7 2915 10th Ave N E Calgary Alberta T2A 5L4 CANADA Phone 866 945 6236 WILO CDN FAX 403...

Отзывы: