Commissioning
68
WILO SE 2019-07
8.2
Activating the device
NOTICE! Rotating field monitoring and motor current monitoring are only available
in the Wilo-Control EC-Booster!
NOTICE
Integrated rotating field monitoring
The switchgear is equipped with rotating field monitoring. The monitoring functions
only operate without faults for three-phase current connections with a clockwise
rotating field. If the mains connection has a counter-clockwise rotating field, the er-
ror code “E006” will appear on the display on activation.
NOTICE
Error message during operation with alternating current connection
The “Control EC-Booster” switchgear is equipped with rotating field monitoring and
motor current monitoring. Both monitoring functions are activated at the factory
and only operate without issues for a three-phase current connection. If the
switchgear is used for an alternating current connection, the following error mes-
sages are shown in the display:
• Rotating field monitoring: Error code “E006”
⇒ To switch off rotating field monitoring: Select “off” in Menu 5.68!
• Motor current monitoring: Error code “E080.x”
⇒ To switch off motor current monitoring: Select “off” in Menu 5.69!
▶ Monitoring functions are deactivated. The switchgear now functions without prob-
lems when using an alternating current connection.
NOTICE
Observe the error code on the display
If the red fault LED lights up or flashes, observe the error code on the display! If the
error has been confirmed, the previous error will be stored in menu 6.02.
1
2
3
4
5
Fig. 26:
Start screen
1
Current pump status:
- Number of registered pumps
- Pump activated/deactivated
- Pumps On/Off
2
Field bus active
3
Actual pressure value
4
Control mode (e.g. p-c)
5
Standby pump function activated
‡
Switchgear is closed.
‡
Installation has been performed correctly.
‡
All signal transmitters and consumers are connected and installed in the operating
space.
‡
If a low-water cut-out switchgear (dry-running protection) is available, the
switching point has been correctly set.
‡
Motor protection is preset according to the pump data (“Control EC-Booster”
only).
1. Turn the main switch to the “ON” position.
2. Switchgear starts.
All LEDs light up for 2 s.
– The display illuminates and the start screen appears.
- The standby symbol appears in the display.
▶ The switchgear is ready for operation. Start the initial configuration or automatic
mode.
Содержание Control EC-Booster
Страница 2: ......
Страница 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Страница 434: ...hr Dodatak 434 WILO SE 2019 07 Legenda R samo pristup za čitanje RW pristup za čitanje i pisanje ...
Страница 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Страница 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Страница 736: ...pt Anexo 736 WILO SE 2019 07 Legenda R só para acesso de leitura RW acesso de leitura e escrita ...
Страница 1208: ......
Страница 1209: ......
Страница 1210: ......