background image

Model 375, 375XL

Reduced Pressure Principle (3/4"-1")

CAUTION:  Installation of Backflow Pre

-

venters must be performed by qualified, 

licensed personnel. The installer should 

be  sure  the  proper  device  has  been 

selected for the particular installation. 

Faulty  installation  could  result  in  an 

improperly functioning device.

WILKINS  Model  375  Reduced  Pressure 

Principle Backflow Preventers are for use 

on  potable  water  lines  where  a  health 

hazard could exist if a backflow situation 

were to occur.

Proper  performance  is  dependent  upon 

following  these  installation  instructions 

and prevailing governmental and industry 

standards  and  codes.  Failure  to  do  so, 

according  to  WILKINS  Limited  Warranty 

"...releases WILKINS of any liability that it 

might otherwise have with respect to that 

device." Such failure could also result in 

an improperly functioning device.

Damage to the device could result wherever 

water hammer and/or water thermal expan

-

sion could create excessive line pressure. 

Where  this  could  occur,  shock  arresters 

and/or  pressure  relief  valves  should  be 

installed downstream of the device.

1.    Before installing a Model 375 Backflow 

Preventer, flush the line thoroughly to remove 

all debris, chips and other foreign matter. If re

-

quired, a strainer should be placed upstream 

of the Backflow Preventer.

CAUTION:  

Do not use a strainer in sel

-

dom used emergency waterlines such 

as fire lines.

2.    Provide  adequate  space  around  the 

installed unit so that the test cocks will be 

accessible for testing and servicing.

3.  

WARNING:

  

If installation of a Model 

375 is in a building, a suitable drain ar

-

rangement  

MUST

 be provided to drain 

off spillage from the relief valve.  An air 

gap at least two times the pipe diameter 

must be provided between the relief valve 

and the drain piping to prevent a cross-

connection. Air Gap AG-11 not intended 

to support weight of drain pipe. 

CAUTION:  

Do not pipe the relief valve 

solidly to a floor drain, sewer or sump.

CAUTION:

   An adequately sized drain is 

required to prevent possible water dam

-

age due to relief valve discharge.

375 REDUCED PRESSURE PRINCIPLE

1.  Start with both shut-off valves closed. 

Slowly open the inlet shut-off valve until the 

backflow preventer is completely pressur

-

ized. A brief discharge from the relief valve 

may occur while the device is pressurizing. 

The discharge should cease by the time the 

shut-off valve is fully open. Device should 

function properly. If the discharge does not 

stop, refer to "MAINTENANCE INSTRUC

-

TIONS" for repair procedures.

2.   After the device has been pressurized, 

vent all trapped air from both check valves 

by slightly opening each of the four test 

cocks.

3.    Slowly  open  the  downstream  shut-off 

valve.  The  Model  375  Reduced  Pressure 

Principle  Backflow  Preventer  is  now  in 

service.

4.   If "spitting" or intermittent discharges 

from  the  relief  valve  are  noted,  it  could 

be a result of pressure fluctuation and/or 

a water hammer condition in the system. 

If such conditions exist, install a WILKINS 

water pressure reducing valve, a WILKINS 

Model 40XL check valve, or a WILKINS 

Model 1250 water hammer shock arrest

-

ers in compliance with industry standards 

as needed.
5.     After  the  Model  375  has  been  prop

-

erly installed, test the device (see "TEST 

PROCEDURES").  If  the  device  fails  the 

test, remove the first and second check  

valves and thoroughly flush the device. If 

the  relief  valve  fails  to  operate  properly, 

inspect the sensing passage for clogging 

(see "MAINTENANCE INSTRUCTIONS"). 

Clean rubber seals of all debris and place 

unit back in service.

4.   Install valve at least 12 inches above

surrounding flood level.

5.    Always consult local codes for installa

-

tion methods, approvals and guidance.

OUTDOOR INSTALLATION

Model 375 Backflow Preventers may be 

installed  outdoors  only  if  the  device  is 

protected  against  freezing  conditions. 

Exposure to freezing conditions will result 

in  improper  function  or  damage  to  the 

device. The installation location must be 

kept above 32°F. All the basic installation 

instructions apply.

If installation is in a pit or vault, the Back

-

flow Preventer must never be submerged 

in water because this will cause a cross-

connection. Make sure that the pit or vault 

always  remains  dry  by  providing  ample 

drainage.

INDOOR INSTALLATION

Indoor  installation  is  preferred  in  areas 

that are subject to freezing conditions. All 

the basic installation instructions apply to 

such installations.

PARALLEL INSTALLATION

Where uninterrupted service from a single 

meter connection must be maintained, two 

or more Backflow Preventers may be con

-

nected in parallel. All the basic installation 

instructions  apply  to  parallel  installation. 

Be sure to allow adequate room between 

the units for testing and repair.

PLACING THE DEVICE IN SERVICE

After the installation of a Model 375 has 

been completed, place the unit in service 

as follows:

a             company

®

Proposition 65 Warning This product contains chemicals known to the State of California 

to cause cancer or birth defects or other reproductive harm.

1

a            

®

 company

 Installation 

 Testing 

 Maintenance Instructions

FLOO

R

DRAI

N

 

I

NLET SHUT OFF

DIRECTION OF FLOW

12" MIN

.

30” MAX.

AIR GA

P

OPTIONAL

   WATE

R

   METER

175 PSIG 180ß F

3/4" 375 RP

ZURN

WILKINS

          2” PIPE

(DRAIN LINE CA

N

BE AN

Y ST

ANDARD

PIPING MATERIAL)

PROTECTIVE

ENCLOSURE

Содержание 375XL

Страница 1: ... all trapped air from both check valves by slightly opening each of the four test cocks 3 Slowly open the downstream shut off valve The Model 375 Reduced Pressure Principle Backflow Preventer is now in service 4 If spitting or intermittent discharges from the relief valve are noted it could be a result of pressure fluctuation and or a water hammer condition in the system If such conditions exist i...

Страница 2: ...l all air is expelled 5 Close by pass valve A Open by pass valve B and bleed to atmosphere until all air is expelled Close by pass valves B and C 6 Attach the VENT hose to test cock 4 7 Slowly open by pass valves A and C and keep by pass valve B closed 8 Open test cock 4 9 Indicated pressure differential will drop slightly If pressure differential does not continue to decrease the 2 check valve is...

Страница 3: ...Fouled 1 check 2 Fouled relief valve seat 3 Fouled 2 check In summation the amount of discharge is proportional to degree of fouling Most problems occur in the 1 check which is where debris enters the backflow preventer first Troubleshooting When the relief valve discharges intermittently it can be almost always assumed that the device is functioning correctly and that the discharge is caused by s...

Страница 4: ...re valve housing check assemblies clamp sleeve and o rings in sealed plastic bag during winter to prevent weathering To Flush System during installation use the following procedures 1 Install backflow device in pipe system leave water off 2 Remove the black backflow preventer housing from the bronze body 3 Install the orange Blow Out Flush fitting into the bronze body 4 Thread a garden hose adapte...

Отзывы: