Operating instructions magnetostrictive level transmitter, models FLM-CA, FLM-CM
16
5.2.3 Wiring with cable gland
The wiring should only be carried out in the unpowered state.
Carry out the wiring of the level transmitter as follows:
1. Unscrew the probe head cover
using an open-ended spanner.
2. Loosen the union nut
of the cable gland
.
3. Thread the 2-wire cable
into the union nut
and tighten (outer diameter: 5 … 10 mm).
4. Remove the screw terminal
.
5. Connect the 2-wire cable
to the poles marked with (+) and (–) on the screw terminal
.
6. Re-affix the screw terminal
. The cable must not have any tension!
7. If required, set reference points (see chapter 5.3.1 “Measuring span on the level
8. Screw the probe head cover
back down.
Removable screw terminal
5. Commissioning, operation