EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
95
Instance 7
Attributes 1 to 50 of instance 7 represent the
input data blocks 1 to 5
in samosPLAN
6. They re-
present the data transferred by the PLC to the logic of the controller module.
Attributes 1 to 50 of instance 7 possess the same data as assembly instance 37, byte 0 to 49.
NOTICE
You can find an explanation of the technical terms used below here:
Table 64: Overview of th vendor-specific object (Wieland Electric, 0x78), supported by the SP-COP2-ENI module
Class Instance
Attribute
Access
Data type
Description
Data range
120
0 = Class
1
Read
UINT
Revision of the class
1
120
0 = Class
2
Read
UINT
Max. instance
4
120
0 = Class
3
Read
UINT
Number of instances
4
120
0 = Class
5
Read
UINT[3]
List of optional services
{2, 0x4c, 0x4d}
120
0 = Class
6
Read
UINT
Max. class attribute ID
7
120
0 = Class
7
Read
UINT
Max. instance attribute ID
60
120
1
n+1
Read
USINT
The input byte “n”, configured
by the
output data set 1
in
samosPLAN
6, stands for the
data transferred by the logic of
the controller module to the
PLC.
n = 0 to 49.
0 to 255
120
2
1
Read
UDINT
Project file CRC (data set 2)
0 to 2
32
-1
120
2
2 to 8
Read
UDINT
Reserved (data set 2)
0
120
3
n+1
Read
BYTE
State byte “n” of the controller
module,
for which n = 0 to 59
0 to 255
120
4
n+1
Read
BYTE
Additional byte “n” of the con-
troller module,
for which n = 0 to 59
0
120
5
1
Read
USINT
SP-COP2-ENI System mode
(
1, 2, 3, 4, 5, 7, 21
120
6
n
Read
UDINT
Error code in the controller
module,
with n = 1 for the most recently
occurred error, n = 2 for the
previous error, etc., with n = 1 to
5
0 to 2
32
-1
120
6
1
Write
UDINT
Clear error list in instance 6
0
120
7
n+1
Write,
read
BYTE
Output bit “n”, which is configu-
red by the
input data blocks 1
to 5
in samosPLAN
6, stands for
the data transferred by the PLC
to the logic of the controller
module. n = 0 to 49.
0 to 255
8.4.8.7