EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
84
Further information:
• Table
Overview of assembly databytes of the SP-COP2-ENI module [ch. 8.5.1, p. 97]
• Figure
Data flow with usage of Assembly Instances [ch. 8.6.2, p. 101]
(Shows the data flow in front of the PLC to the module SP-COP2-ENI and back from the point of
view of the individual assemblies.)
Table 42: Overview of the assembly class (0x04) supported by the SP-COP2-ENI module
Class Instance Attribute Access
Data type
Description
Data range
4
0 = Class
1
Read
UINT
Revision of the class
2
4
0 = Class
2
Read
UINT
Max. instance
167
4
0 = Class
3
Read
UINT
Number of instances
7
4
0 = Class
6
Read
UINT
Max. class attribute ID
7
4
0 = Class
7
Read
UINT
Max. instance attribute ID
4
4
37
1
Read
UINT
Number of members
0
4
37
3
Read,
write
BYTE[50]
Bits of the logic outputs [ch. 8.5.2, p.
99]
(Instance 1 to 400 of Class 9)
See
1)
4
37
4
Read
UINT
Number of data bytes
50
4
57
1
Read
UINT
Number of members
0
4
57
3
Read
BYTE[67]
Input bits (Instance 1 to 528 of Class
8)
See
1)
4
57
4
Read
UINT
Number of data bytes
67
4
138
1
Read
UINT
Number of members
0
4
138
3
Read,
write
BYTE[40]
Bits of the logic outputs [ch. 8.5.2, p.
99]
(Instance 81 to 400 of Class 9)
See
1)
4
138
4
Read
UINT
Number of data bytes
40
4
139
1
Read
UINT
Number of members
0
4
139
3
Read,
write
BYTE[30]
Bits of the logic outputs [ch. 8.5.2, p.
99]
(Instance 161 to 400 of Class 9)
See
1)
4
139
4
Read
UINT
Number of data bytes
30
4
140
1
Read
UINT
Number of members
0
4
140
3
Read,
write
BYTE[20]
Bits of the logic outputs [ch. 8.5.2, p.
99]
(Instance 241 to 400 of Class 9)
See
1)
4
140
4
Read
UINT
Number of data bytes
20
4
141
1
Read
UINT
Number of members
0
4
141
3
Read,
write
BYTE[10]
Bits of the logic outputs [ch. 8.5.2, p.
99]
(Instance 321 to 400 of Class 9)
See
1)
4
141
4
Read
UINT
Number of data bytes
10
4
167
1
Read
UINT
Number of members
0
4
167
3
Read
BYTE[112]
Bits of the logic inputs, mode and
state bytes
(
See
1)
4
167
4
Read
UINT
Number of data bytes
112
1)
See: Table
Overview of assembly databytes of the SP-COP2-ENI module [ch. 8.5.1, p. 97]
Discrete Input Point Object
79995019
The discrete input point objects are part of the device profile
Discrete universal I/O device.
8.4.3