5
Feeding into a power bus segment and power tapping
24
Wieland Electric GmbH | BA000369 (Rev. B) | 02/2016
Limit values of current-carrying capacity [A] of
podis
®
CON
connection components on the flat cable
EVA 7 x 4 mm², valid for connection module (75.018.0051.2) and flat cable outlet, pluggable
(75.015.5153.1):
Example for feeding
Assuming a maximum ambient temperature of 30°C, it is, for example, possible to feed up to 35 A for the
cable section (400 VAC, contact points 1-3) and 20 A for the auxiliary conductors (24 VDC, contact points
5 and 6). This example assumes a symmetrical load (no current on neutral conductors or contact point 4).
Mounting of connection and tapping modules
Connection modules and flat cable outlets can be placed on both sides of the flat cable due to its sym-
metrical properties. The flat cable is inserted with the correct coding, the top section is closed and then
screwed into place. The mounting is demonstrated by means of a fixed connection module. The assem-
bly of a pluggable outlet is handled in the same manner.
Screw the module to the base using suitable screws, for example M4.
Only use the slotted holes intended for this purpose.
Open up the top section and place the flat cable into it.