Application of this type of control may cause flame 
rollout on initial startup and could cause personal 
injury and/or property damage.
Replace only with exact model number, including dash 
number.  Failure to use exact replacement control could 
cause personal injury and/or property damage.

If in doubt about whether your wiring is millivolt, line, or low volt-
age, have it inspected by a qualified heating and air conditioning 
contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes 
and ordinances.
This control is a precision instrument, and should be handled 
carefully. Rough handling or distorting components could cause 
the control to malfunction.

50V64-743

Integrated Furnace Control

for Furnaces with Variable Fan Speed

INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL 
INJURY AND/OR PROPERTY DAMAGE.

CONTENTS

Description ............................................................. 1

Precautions ............................................................ 1

Specifications ......................................................... 2

Operation ................................................................ 2

Installation .............................................................. 5

 

Mounting & Wiring

The 50V64-743 is a two-stage automatic gas interrupted ignition 
control employing a microprocessor to continually monitor, 
analyze, and control the proper operation of the gas burner and 
inducer, and provide signal for proper operation of variable fan 
speed timing.
Signals interpreted during continual surveillance of the two-
stage thermostat and flame sensing element initiate automatic 
ignition of the burner, sensing of the flame, and system shutoff 
during normal operation.
The control incorporates system fault analysis for quick gas 
flow shutoff, coupled with automatic ignition retry upon sensing 
a fault correction.

PART NO. 37-7565A

1503

www.white-rodgers.com

www.emersonclimate.com

 DESCRIPTION

 PRECAUTIONS

GENERAL PRECAUTION

!

To prevent electrical shock and/or equipment damage, 
disconnect electric power to system at main fuse or 
circuit breaker box until installation is complete.
This control is not intended for use in locations where 
it may come in direct contact with water. Suitable 
protection must be provided to shield the control from 
exposure to water (dripping, spraying, rain, etc.).
Label all wires prior to disconnection when servicing 
controls. Wiring errors can cause improper and 
dangerous operation.
Following installation or replacement, follow appliance 
manufacturers’ recommended installation/service 
instructions to insure proper operation.
Do not use on circuits exceeding specified voltage. 
Higher voltage will damage control and could cause 
shock or fire hazard.

CAUTION

!

WARNING

!

Do not short out terminals on gas valve or primary 
control to test. Short or incorrect wiring will damage 
thermostat and could cause personal injury and/or 
property damage.

Содержание 50V64-743

Страница 1: ...burner and inducer and provide signal for proper operation of variable fan speed timing Signals interpreted during continual surveillance of the two stage thermostat and flame sensing element initiat...

Страница 2: ...amp 80VAC 60 Hz resistive Humidifier Relay 1 0 Amp 120 VAC 60 Hz Electronic Air Cleaner Relay 1 0 Amp 120 VAC 60 Hz Flame Current Requirements Minimum current to insure flame detection 1 A DC Maximum...

Страница 3: ...into the retry sequence The retry sequence starts with a 60 second interpurge en abling the inducer at low speed for 60 seconds following an unsuccessful ignition attempt flame not detected After thi...

Страница 4: ...flashes the error codes The last four fault codes can be erased from memory by pow ering up with G energized and then toggling W1 three times within eight seconds W1 must be toggled after the power ON...

Страница 5: ...de Humidifier hot side Electronic Air Cleaner hot side Humidifier neutral side Electronic Air Cleaner neutral side Flame probe maximum recommended flame probe wire length is 36 inches IND 01 1 IND 02...

Страница 6: ...S VALVE HIGH LIMIT N C PS1 N O PS2 N O ROLLOUT N C Inducer Limit N C FLAME SENSOR PROBE CONDENSING UNIT CIRCULATOR INDUCER 24 VAC 120 VAC 24 VAC CLASS II TRANSFORMER HOT LINE NEUTRAL LINE TH TR Low Vo...

Страница 7: ...7 NOTES...

Страница 8: ...White Rodgers is a business of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co www white rodgers com www emersonclimate com...

Страница 9: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information White Rodgers 50V64 743...

Отзывы: