For Service Technician Use Only
DIAGNOSTICS (Cont.)
Wine Center
n
2-3
Error Codes
Code
Faulty description
Faulty checking
Faulty repairing
E1
T1 sensor open circuit
Check the wiring and connection between
PCB and sensor, if it is open circuit.
If the connection and wiring are normal, replace
the sensor.
E2
T1 sensor short circuit
Check the wiring and connection between
PCB and sensor, if it is open circuit.
E3
T2 sensor open circuit
Check the wiring and connection between
PCB and sensor, if it is open circuit.
E4
T2 sensor short circuit
Check the wiring and connection between
PCB and sensor, if it is short circuit.
HI
Inner temperature too high
1.
Display on both compartment:
a.
Check if any refrigerant leakage.
a.
Repair the leakage.
b.
Check if the capillary jam.
b.
Clean or replace the capillary.
c.
Check the evaporator fan.
c. Replace the evaporator fan.
2.
Display on lower compartment: Check
the lower fan
If the fan is broken, replace it.
LO&CL
Inner temperature too low
Check if the PCB is normal.
Replace the PCB.
Operating Temperature and Pressure
NOTES:
Ƀ
Engineering Model Numbers with R134a gas -
Follow normal sealed system purging, capturing, brazing, and charging procedures
for models: WUW35X15DS01, WUW35X24DS01, WUW55X15DS01, WUW55X24DS01, WUW55X15HS00, and WUW55X24HS00.
Ƀ
Engineering Model Numbers with R600a gas (new compressor and PCB) -
Follow R600a sealed system purging, capturing, lokring,
and charging procedures outlined in Service Manual
for models: WUW35X15DS02, WUW35X24DS02, WUW55X15HS01,
and WUW55X24HS01.
Range of operating temperature and pressure
Component
Temp (°C)
Temp (°F)
MPA
KPA
PSI (gauge)
R600a Evap
-25°C to -18°C
-13°F to 0°F
0.06 MPa to 0.08 MPa
60 KPa to 80 KPa
-6 psig to -3 psig
R600a Condenser
37°C to 47°C
99°F to 117°F
0.5 MPa to 0.65 MPa
500 KPa to 650 KPa
57.8 psig to 79.6 psig
R134a Evap
-21°C to -18°C
-6°F to 0°F
0.127 MPa to 0.145 MPa
127 KPa to145 KPa
3.7 psig to 6.3 psig
R134a Condenser
41°C to 47°C
106°F to 117°F
1.044 KPa to 1.221 KPa
1044 KPa to 1221 Kpa
136.3 psig to 162.3 psig
*Operating pressures and temperatures specific to these products.
Содержание WUW35X15DS
Страница 1: ...SERVICE MANUAL Wine Center W11403592 ...
Страница 4: ...iv n Wine Center Notes ...
Страница 14: ...GENERAL INFORMATION 1 10 n Wine Center Notes ...
Страница 20: ...DIAGNOSTICS 2 6 n Wine Center Notes ...
Страница 30: ...For Service Technician Use Only COMPONENT TESTING 3 10 n Wine Center Notes ...
Страница 42: ......