INSTALLATION INSTRUCTIONS
SERIES SM AND SMX SYNCHRONIZATION (SYNC) MODULE
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Sync Modules (Series SM) are uniquely designed to accept two independent strobe and audible inputs and convert to a
single output that connects to Wheelock’s Series AS and NS appliances. When interfaced with the sync module, the audible strobes
produce the synchronized code 3 horn and synchronized strobe upon actuation. The audible portion of the AS and NS can be
controlled independently from the strobe, using only a 2-wire alarm circuit. They are the ideal choice for alarm systems where an
audible silencing feature is required during an alarm condition. The SM is UL Listed under Standard 1971 (Emergency Appliances
for the Hearing Impaired) for indoor use Fire Protective Service and ULC Listed under CAN/ULC-S525-99 for Audible Signaling
Appliances for Fire Alarm Systems. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit
wiring by a Fire Alarm Control Panel (FACP).
The table below shows the additional Wheelock products that can be used with the SM Sync Modules.
Table 1: Products Available for Use with SM Sync Module
Series AH/AH-WP, NH, HS
Audible Horn
Series MT with Strobe
Multitone Horn with Sync Strobes
Series E70/90 with Strobe
E Speakers with Sync Strobe
Series ET70/90/1080/1081 with Strobe
ET Speakers with Sync Strobe
Series RSS/RSSP Strobes
Remote Sync Strobes
Series CH70 Strobes
Chimes with Strobes
Series AS, NS, HS4
Audible Horn with Sync Strobes
NOTE
:
All
CAUTIONS
and
WARNINGS
are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: THE SM APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
NOTE
: All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems -
CAN/ULC-S524-01 and Canadian Electrical Code, Part 1. Final acceptance is subject to Authorities Having Jurisdiction.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE
FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION
AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 2: Ratings Per UL and ULC
Model
Regulated
Voltage
(VDC/VRMS)
Voltage Range Limit
Per UL 1971
(VDC/VRMS)
Voltage Range Per
CAN/ULC-S525-99
(VDC/VRMS)
Mounting
Option
SM-12/24 12/24 8.0-33.0 10.5-31.0 A
SMX-12/24 *
12/24
8.0-33.0
10.5-31.0
----
* SMX is a UL recognized component; SMX is a ULC Listed model.
The SMX version does not have a mounting plate.
WARNING: FOR UL APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 8.0-
33.0 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF
THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: FOR ULC APPLICATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE OF 10.5-31.0
VOLTS FOR 24V MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). APPLY 80% AND 110%
OF THESE VOLTAGE VALUES FOR SYSTEM OPERATIONS.