SERIES ET70/90 LOW PROFILE HIGH INTENSITY SPEAKER STR

OBES

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 

Wheelock’s Series ET70/90 Low Profile High Intensity Speaker Strobes are UL Listed under Standard 1971 for Signaling Devices for 
the Hearing Impaired and UL Standard 1480 for Speaker Appliances.  They are designed for multiple power requirements with high 
dBA output at each power tap.  All models offer a choice of field selectable taps, 1/8W to 8W for either 25.0VRMS or 70.0VRMS 
audio systems.  The Low Profile design incorporates a high efficiency speaker for maximum output at minimum power across a 
frequency range of 400Hz to 4000Hz, and features a sealed back construction for extra protection and improved audibility.  The 
Series ET appliances also incorporate a Speaker Mounting Plate attached to the speaker for ease of installation. The Low Profile 
Speaker Strobes can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or 
provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or 
Wheelock’s Power Supplies.  The Strobes use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan

 lens to 

provide maximum visibility and reliability for effective visible signaling. 

 

NOTE

:  “Lexan” is a registered trademark of General Electric Corporation. 

 

NOTE

:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital letters. 

 

WARNING:  READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY 
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 
SPECIFICATIONS: 

 

Table 1:  UL Listed Models and Ratings 

 Speaker 

Strobe 

 

 

 

dBA at 10 Feet 

Regulated Voltage 

 

Mounting 

Models Voltage 

(Rated 

Watts) 

(VDC/VRMS) 

Candela 

Options 

 

(VRMS) 1/8 1/4 1/2 1 2 4 8 Min 

Nom 

Max   

 

ET70-24150W  25/70 

75  78  81 84 87 90 93 ----  ----  ----  150 

A,B 

ET70-24177W  25/70 

75  78  81 84 87 90 93  16  24  33  177 

A,B 

ET70-24185W  25/70 

75  78  81 84 87 90 93  16  24  33  185 

A,B 

ET70-24150C 

25/70 

75  78  81 84 87 90 93  16  24  33  150 

A,B 

ET70-24177C 

25/70 

75  78  81 84 87 90 93  16  24  33  177 

A,B 

ET90-24150W  25/70 

75  78  81 84 87 90 93  16  24  33  150 

ET90-24177W  25/70 

75  78  81 84 87 90 93  16  24  33  177 

ET90-24185W  25/70 

75  78  81 84 87 90 93  16  24  33  185 

ET90-24150C 

25/70 

75  78  81 84 87 90 93  16  24  33  150 

ET90-24177C 

25/70 

75  78  81 84 87 90 93  16  24  33  177 

 

NOTES

1.  Strobes will produce 1 flash per second over the “Regulated Voltage” range. 
2.  All models are UL Listed for indoor use with a temperature range of +32

°

F to +120

°

F (0

°

C to +49

°

C) and maximum humidity of 

85% RH. 

3.  dBA is rated per UL Standard 1480 for Speaker Appliances. 

 

NOTE:  THE MAXIMUM WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.  THE MAXIMUM 
NUMBER OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47. 

 

WARNING:  THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING 

FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR).  DO NOT APPLY 80% AND 110% OF THESE 
VOLTAGE VALUES FOR SYSTEM OPERATION. 

 

Copyright 2003 Wheelock, Inc.  All rights reserved. 

Содержание ET70-24150W

Страница 1: ...identified by the symbol All warnings are printed in bold capital letters WARNING READ THESE INSTRUCTIONS CAREFULLY FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COUL...

Страница 2: ...WER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR O...

Страница 3: ...45 0 67 53 1 77 45 0 67 53 1 77 55 5 90 85 37 5 72 44 3 81 37 5 72 44 3 81 46 3 68 90 37 5 55 44 3 64 37 5 55 44 3 64 46 3 63 Table 3A Vertical Plane Vertical 150C 177C 150W 177W 185W Angle in deg UL...

Страница 4: ...THEY ARE INSTALLED THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE WHICH COULD RESULT IN PROPERTY DAMAGE A...

Страница 5: ...if sheathed multiconductor cable or 3 4 conduit fittings are used 1 ET70 90 models have an integrated Speaker Mounting Plate 2 The Speaker Mounting Plate must be oriented correctly when it is mounted...

Страница 6: ...FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS STANDARDS REGULATIONS CODES AND GUIDELINES NOTE NFPA 72 ANSI 117 1 conform to ADAAG Equivalent Facilitation Guidelines...

Страница 7: ...NDITIONS BEYOND MANUFACTURER S CONTROL SOME OF THE MANUFACTURER S PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS THE MANUFACTURER DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE...

Отзывы: