background image

Instructions for 

Digitrip RMS 500 Trip Unit 

Table  of  Contents 

1 .0 

General  Description . . .... ...... . . .. ... ..... . . 

1 .1 

Protection .... . .. . ... ........... . .. ......... . 

1.2 

Information . ... .. .... . ... . ... . ... ... ..... .. . . 

1 . 3 

Testing . . ... .. . .. . ... . ... . ... . ... ... . . ... ... . 

2. 0 

UL  Listed  Devices . ... .... . . .. . ... ... .. . .. ... . 

3 . 0  

Principle  of  Operation . . ... . ... .... . . ..... ... . 

3.1 

General  .... . ..... . ... . .. . .... . ... .. . .. .. ... . 

3.2 

Trip  and  Operation  Indicators .. . ... ... .. .. ... . 

3.3 

Test  Provisions  . ....... . ... .... ... ..... ... .. . 

3. 4 

Making Current  Release  (Discriminator)  .... .. . 

3.5 

Instantaneous  Override  . ........... . . ... .... . 

3.6 

Zone  Interlocking ... .... . ... ....... ... .. . . . .  . 

4.0 

Protection  Settings .. . .... ... . ...... . .. . . ... . . 

4.1 

General  ... ... ... ... . .. . . ...... . ... ... ..... . . 

4.2 

Long  Delay  Settings  ..... . ... .... .......... .  . 

4.3 

Long  Delay  Time  Settings .... . ........ ... ... . 

4.4 

Short  Delay  Pick-up  Settings  ........ ... .. ... . 

4.5 

Short  Delay  Time Settings  . ... ......... .. . .. . 

4.6 

Instantaneous  Pick-up  Settings  . ... ... .. ... .. . 

4.7 

Ground  Fault  Current  Pick-up  Settings  ....... . 

4.8 

Ground  Fault  Time  Delay  Settings  . ...... . . .. . 

5.0 

Integral  Test  Panel  - Test  Procedure  ... .. ... . . 

5.1 

General  .. ... .... ... . ... .... .......... .. ... . . 

5.2 

When To  Test  ....... ... .... ....... ... ..... . . 

5.3 

Test  Provision  ....... ... . .... ......... . . ... . . 

5.4 

Mode  of  Conducting  Tests  ... ......... ... .. . . 

5. 4.1 

Control Power ... .... .... . ....... . . . .. ... ... . 

5. 4.2 

By Not  Tripping  the  Breaker ...... ... ..... ... . 

5. 4.3 

By  Tripping  the  Breaker ....... ... ... ... ..... . 

6 . 0  

Back-up  Battery .... ... ........ ... ... ... ... .. . 

6 . 1  

General  . ... ... ... . ... ..... ... . ... .. . .... . .. . 

6. 2 

Battery Check  .. ... .... ........ ... ..... ..... . 

6. 3 

Battery  Replacement ........... ... . . . ....... . 

7.0 

Auxiliary  Power  Module . .... ... ...... ..... .. . 

8.0 

Rating Plug .. ... . ... .... .... ... ... ... ... . . .. . 

9. 0 

References  . . ... . ... ........ ... ... . .. . . . .. .. . 

9.1 

Type  DS  Low  Voltage  AC  Power  Circuit 

Breakers  .. .... .... ........... ... ... ...... . 

9.2 

Type  SPB  Systems  Pow-R  Breakers ......... .  . 

9.3 

Digitrip  RMS  Trip  Assemblies  .... ... .. ..... . . 

9.4 

Series  C® R-Frame  Molded  Case Circuit 

Breakers  ....... . ... ..... . .. ........... ... . 

WARNING 

DO NOT ATTEMPT TO INSTALL OR PERFORM MAIN­
TENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. 

DEATH OR SEVERE PERSONAL INJURY CAN RESULT 

FROM  CONTACT  WITH  ENERGIZED  EQUIPMENT. 
ALWAYS  VERIFY  THAT  NO  VOLTAGE  IS  PRESENT 

BEFORE  PROCEEDING  WITH  THE  TASK,  AND 
ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY 
PROCEDURES .   THE  WESTINGHOUSE  ELECTRIC 
CORPORATION  IS  NOT  LIABLE FOR THE MISAPPLI­
CATION OR MISINSTALLATION OF  ITS PRODUCTS. 

Page 
























1 0  
1 0  
1 0  
1 0  
1 0  
1 0  
1 1  

1 1  
1 1  
1 1  

1 1  

The  user  is cautioned to observe all recommendations, warn­
ings and cautions relating to the safety of personnel and equip­
ment,  as  well  as  all  general  and  local  health  and  safety laws, 
codes, and  procedures. 

The  recommendations  and  information  contained  herein  are 
based on Westinghouse experience and judgement, but should 

Effective  May,  1 98 9  Supersedes  I.L. 2 9-8 5 1   dated  March,  1 988 

I.L. 

29-851 -A 

not  be  considered  to  be  all-inclusive  or  covering  every  appli­
cation or circumstance which may arise. lf any questions arise, 
contact  Westinghouse  Electric  Corporation  for  further  infor­
mation  or instructions. 

1 . 0   General  Description 

1 . 1   Protection 

The Digitrip RMS  5 00 Trip Unit, illustrated in Fig. 1 ,  is a micro­
processor based type trip suitable for use in type SPB Systems 
Pow-R  circuit  breakers  and  types  DS and  DSL  low voltage AC 
power  circuit  breakers  and  Series  C®  R-Frame  molded  case 
circuit  breakers. 

The  trip  unit  provides  true  RMS  current  sensing  for  proper 

correlation  with  thermal  characteristics  of  conductors  and 
equipment. Interchangeable rating plugs are provided to estab­
lish  the  continuous current  rating  of  each  circuit  breaker. 

The  Digitrip  RMS  5 00 Trip  Unit  is  completely  self-contained 
and  when  the  circuit  breaker  is  closed,  requires  no  external 
control  power  to  operate  its 

protection  systems. 

It  operates 

from  current  signal  levels  and control power  derived through 
current  sensors  integrally  mounted  in  the  circuit  breaker. 

The Digitrip RMS  5 00 Trip Unit is available in six optional pro­
tection  models. Each  trip  unit  may  be  equipped  with  a  maxi­
mum of five phase and two ground  (time-current) adjustments 
to  meet  specific  application  requirements. These  protection 

models  include  the  following  types  which  are  further  illus­
trated  in  the  nameplate  examples  shown  in  Fig. 2. 

Figure 

Type Protection 

2. 1 

Long  Time/Instantaneous 

2.2 

Long  Time/Short  Time 

2.3 

Long  Time/Short  Time/Instantaneous 

2.4 

Long Time/Instantaneous/Ground 

2. 5 

Long  Time/Short  Time/Ground 

2 . 6 

Long  Time/Short  Time/Instantaneous/ 
Ground 

1.2  Information 

Identifier 

(LI) 
(LS) 
(LSI) 
(LIG) 
(LSG) 
(LSI G) 

Red  LED  indicators  are  provided  on  the  face  of the  trip unit 

to indicate  the mode  of an  automatic  trip  operation. A  bat­
tery  is  provided  to maintain  the  mode  of trip  LED  indication 
following  an  automatic  trip  operation. 

Green  LEOs  are  provided  to  indicate  the  operational  status  of 
the  trip unit  and the  status of the back-up battery  mounted in 
the  rating  plug. 

1 .3  Testing 

An integral test panel, including a test selector switch and test 
and  reset  pushbuttons,  is  provided  to  test  the circuit breaker 
in  either  a  "Trip"  or  "No-Trip"  test  mode  under  qualified 
conditions. 

2.0  UL  Listed  Devices 

Digitrip  RMS  5 00  Trip  Units  are  listed  by  the  Underwriters 
Laboratories,  Inc.  for  use  in  types  SPB,  DS  and  DSL  and 
Series C  R-Frame  circuit  breakers under UL File  E7819. 

www 

. ElectricalPartManuals 

. com 

Содержание Digitrip RMS 500

Страница 1: ...act Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 5 00Trip Unit illustrated in Fig 1 is a micro processor based typ...

Страница 2: ...ade m U S A VJ N Lithium Battery Only Long Delay Long Delay Setting Time In IT Sec At 61n 0 0 Breaker Trips In 6 T Test Amps IIJ in 0 Test 0 b Trip o IT In Reset 0 t n us lnst NP156P656H01 Fig 2 1 Lon...

Страница 3: ...P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse Digital Protection D1g1tr1p RMS 500 CeliNa ___ 1NP256P655HOI Made 1n U S A II N L1th1um Battery Only Long Delay LongDelay Set...

Страница 4: ...e pre set protection function pick up settings and other operating data stored in the ROM or Read Only Memory The microcomputer software program is then used in decision tree fashion to initiate prote...

Страница 5: ...with an adjustable instantaneous setting i e types LS or LSG a high set non adjustable instantaneous override trip circuit is provided This high level tripping action is pre set to a specific value t...

Страница 6: ...er in which the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit bre...

Страница 7: ...me _____ I I I I I r Q Sec S 1 1 I I I u M I 1 1 I I I _ j 1 1 f l I I _ Available Settings 0 1 0 2 0 3 0 4 0 5 Seconds with Flat Response I I I m 1 j 1 1 I I w 3 0 1 0 3 0 5 Seconds with l t Response...

Страница 8: ...t all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating In Any attempt to conduct in service testing above this value will b...

Страница 9: ...g 6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fault condition occur during an in service No Trip Test sequence the protection functio...

Страница 10: ...INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliary...

Страница 11: ...ype SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master...

Страница 12: ...Westinghouse Electric Corporation Distribution and Control Busi ness Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Страница 13: ...ntact Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 500 Trip Unit illustrated in Fig 1 is a micro processor based t...

Страница 14: ...0 l Cell No NP156P655H01 Made tn U S A y N Lith1um Battery Only Long Delay Long Delay Setting Time QJ In IT sec At 61n 0 0 Breaker Trips In 6T Test Amps ill In 0 Test 0 Trip 0 I In Reset 0 us lnst NP1...

Страница 15: ...Amps 0 In 0 Test 0 Tnp 0 Reset Unit Status NP156P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse D1g1tal Protection Digitnp RMS 500 Cell No Gnd Fault Pickup In 0 long Delay...

Страница 16: ...dly compared with the pre set protection function pick up settings and other operating data stored in the ROM or Read Only Memory The microcomputer software program is then used in decision tree fashi...

Страница 17: ...not equipped with an adjustable instantaneous setting i e types LS or LSG a high set non adjustable instantaneous override trip circuit is provided This high level tripping action is pre set to a spec...

Страница 18: ...the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit breaker Spe ci...

Страница 19: ...I I Short Delay Time I 1 I I I Sec 0 1 1 I I I u I 1 1 I I I 1 1 1 In Viewing Window Indicates l t Type Response I I l J I I w Fig 4 4 Short Delay Time Settings r 1 I I I I lnst I I In i_ J 0 Availabl...

Страница 20: ...e trip unit all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating In Any attempt to conduct in service testing above this va...

Страница 21: ...Fig 6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fault condition occur during an in service No Trip Test sequence the protection func...

Страница 22: ...O INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliar...

Страница 23: ...pe SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master C...

Страница 24: ...2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Страница 25: ...ntact Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 500 Trip Unit illustrated in Fig 1 is a micro processor based t...

Страница 26: ...No I NP256P655H01 Made in U S A lj3 N Lithium Battery Only Long Delay Long Delay Setting T1me ITJ in I Sec At 61n 0 0 Breaker Trips In 6T Test Amps In 0 Test 0 0 Trtp 0 I In Reset 0 us lnst NP256P656H...

Страница 27: ...lay Time 0 Sec 0 b Ovemde D1scnmlnator Test 0 Trip o Reset NP256P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse D1gital Protection Digitnp RMS 500 Cell No r NP256P655H01 Mad...

Страница 28: ...hich the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit breaker Sp...

Страница 29: ...I I I I I Sec 0 I I I I I u _ M I I t 1 I I I 1 t 1 I I Available Settings 0 1 0 2 0 3 0 4 0 5 Seconds with Flat Response r j I I ill 1 J 1 1 I I w 3 0 1 0 3 0 5 Seconds with l t Response l t Respons...

Страница 30: ...unit all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating Onl Any attempt to conduct in service testing above this value wi...

Страница 31: ...6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fau lt condition occur during an in service No Trip Test sequence the protection function...

Страница 32: ...O INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliar...

Страница 33: ...pe SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master C...

Страница 34: ...2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Отзывы: