HPT-15K/17K/20K/25K USER MANUAL 20
9.
TECHNICAL PARAMETERS
Module
W-HPT-15K
W-HPT-17K
W-HPT-20K
W-HPT-25K
INPUT/DC
Max. PV Power
(
Wp
)
22500
25500
30000
30000
Max. Input Voltage
(
V
)
1000
MPP Voltage Range
(
V
)
200~900
Min. DC Voltage
(
V
)
150
Nominal DC-Input Voltage
(
V
)
620
Max. Input Current
(
A
)
13 per string
Max. short DC current
(
A
)
20 per string
No. of independent MPPT inputs
2
No. of PV strings per MPPT
2
Max. inverter backfeed current to the
array
(
A
)
0
OUTPUT/AC
Rated Power
(
W
)
15000
17000
20000
25000
Max. apparent AC power
(
VA
)
16500
19000
22000
25000
Rated grid voltage
(
Vac
)
380/400
Rated power frequency
(
HZ
)
50/60
Max. output current
(
A
)
24
27.6
31.9
36.3
Max. output overcurrent protection(A)
40
40
40
50
Inrush current (Peak and duration)*
18.4A
@0.214ms
18.4A
@0.214ms
18.4A
@0.214ms
18.4A
@0.214ms
Max. output fault current( Peak and
duration)*
35.5A
@420us
35.5A
@420us
35.5A
@420us
35.5A
@420us
Adjustable displacement power factor
0.8ind to 0.8cap
THDi at rated power
<3%
”*”
The inrush current and Max. output fault current are really test values.
EFFICIENCY