Page 20 of 34
PQP-171-P
5.2.5
CCMODE (Characteristics linearization)
Command
Parameter
Unit
Group
CCMODE
X
x= ON|OFF
-
EXP
This command activates the characteristic linearization function. Deactivating immediately allows an easy and
fast evaluation of the linearization.
5.2.6
SENS (Malfunction monitor)
Command
Parameters
Unit
Group
SENS
x
x= ON|OFF|AUTO
-
STD
This command is used to activate/deactivate the monitoring functions (4… 20 mA sensors, output current, sig-
nal range and internal failures) of the module.
ON:
All monitoring functions are active. Detected failures can be reset by deactivating the ENABLE in-
put.
OFF:
No monitoring function is active.
AUTO:
Auto reset mode. All monitoring functions are active. If the failure doesn’t exist anymore, the mod-
ule automatically resumes to work.
Normally the monitoring functions are always active because otherwise no errors are detectable via
the READY output. Deactivating is possible mainly for troubleshooting.
5.2.7
EOUT (Output signal if not ready)
Command
Parameters
Unit
Group
EOUT X
x= -10000… 10000 0.01 %
EXP
Output value in case of a detected error or a deactive ENABLE input. A value (degree of valve opening) for
use in the event of a sensor error (or the module is disabled) can be defined here. This function can be used if,
for example, the drive is to move to one of the two end positions (at the specified speed) in case of a sensor
error.
|EOUT| = 0
The output is switched off in the event of an error. This is normal behavior.
CAUTION!
The output value defined here is stored permanently (independently of the parameter set). The
effects should be analyzed by the user for each application from the point of view of safety.