background image

 

-- 10 -- 

. Maintenance

 

1. During the daily running, it is required to check all meter’s indication to be in normal range. Avoid rain or too much 

moisture  on  electric  components  which  would  cause  electricity  shorting.  If  such  problem  is  found,  dry  the 

components with care.   

2. Always monitor the working status of compressor and fan motor, make sure the running sound is normal. If there is 

any strange noise or abnormal sound, switch off the machine and call professional maintenance service for checkup 

and repair.   

3.Thermal  expansion  valves  and  other  refrigeration  components  such  as drying  filters, solenoid  valves  in  the  main 

circuit should work normally. Filters, drying filters, main circuit solenoid valves in front of thermal expansion valves

at high pressure

the temperature difference between the inlet and outlet pipes should not be obvious

nor should there 

be dew or frost on components. Replacement of refrigeration components or troubleshooting of refrigeration systems 

must be done by professionals. 

4. Always  check  the  joints  between  various  parts  are  tightened  and  firm,  particularly  the  join  bolts  of  electric 

components  and  conducting  wires  cannot  be  of  any  loose  or  have  moisture.  Make  sure  the  wiring is  tightened  and 

firm. 

5.  Clean  the  surface  of  machine  regularly  to  keep  it  clean.  Do  not  use  any  detergent,  organic  solvent  (e.g.  Lacquer 

Thinner) or other solvents containing acid or alkali to clean the painted surface.   

6. Air filter should be cleaned regularly subject to the local working conditions. Normally it should be cleaned once a 

week. Use soft brush to clear dust first and then clean with water or detergent. Dry it in room air. (See Annex III) 

7. Always  check  the  condenser  if  there  is  dust  or  dirt  on  the  surface.  Clean  the  surface  regularly  with  neutral  warm 

solution and soft brush. Avoid damage to the flakes. 

8.  Always  check  the joins  in  compressor compartment if there is obvious oil stains  or  not. If  such oil  stains found, it 

indicates the cooling gas would be leaking. Call professional service for repair and redo vacuuming and gas filling.   

9.The machine must be upright when loading or handling. If it needs to be inclined, the angle between the machine and 

the ground is no more than 45degrees. 

10. Do not open the cooling system if there is not a breakdown. It does not require adding with cooling gas or grease 

because it’s a totally sealed-off system. If such adding is necessary, it should be handled by professional service. 

 

 

 

 

 

 

 

11. Table of major parts of filtration system 

ITEM NAME

 

SPECIFICATION

 

QUANTITY

 

SERVICE TIME

 

Fabric Filter in Bottom Tank 

 

Φ

40 

2 pcs 

To be cleaned once a month 

 

RO Booster Pump 

 

EC-101-50 

2 pcs 

As required   

CTO Filter 

 

10

`` 

5 pcs 

6 months 

Resin Filter 

 

10

``

 

2 pcs 

6 months 

DOW-RO Membrane

 

TW-1812-50 

2 pcs 

2-3

 years

 

UV 

16W 

pcs 

8000H or 12 months of the bulb

 

Water Output Pump 

 

15WG10-10 

1 pcs 

   

Содержание WES-250

Страница 1: ...aintenance 10 Ⅷ Troubleshooting 11 ANNEX I 13 ANNEX II 18 ANNEX Ⅲ 19 Notice This machine does not install RO film in it by default Please install RO film inside the machine before starting Please follow page 14 CLEAN AND REPLACE RO FILTERS to install The pictures in this instruction manual are only for reference purposes only NOTE There may be technical changes or changes in structural design with...

Страница 2: ...d to electricity 3 Automatic Control The unit is using a control method by a combination of multifunctional CPU micro computer controller enabling the user of a convenient and simple operation by pressing ON or OFF buttons The system uses auto monitoring of internal parts It will give out a warning and stop the system running automatically if the sensors find any issues 2 Product Models 250 L per ...

Страница 3: ... building 1 5 meter for air exhaust Place the machine in a place without direct sunlight and away from heat source preferably covered from rain and sunshine There should not be barrier effecting ventilation around the air inlet and outlet of the machine Do not run the machine in circumstances of alot of dust or serious chemical pollution 2 3 The machine should be equipped with independent power su...

Страница 4: ... out 3 1 3 Switch on the master power supply Check whether the Phase Sequence Detection Indicator is on If the NORMAL light is on it will be normal If the other lights are on it will be restored after the power is cut off and connected correctly 3 1 4 After the master power supply is switched on turn the E STOP button clockwise and the red power lamp will be on Oil heater of compressor automatical...

Страница 5: ... 4 Top Tank Liquid Level Probe UV BALLAST TOP TANK UV Top Tank Filter Drier Access Valve Main Circuit Solenoid Valve ...

Страница 6: ...O Filter RO Backwash Valve IV RO Filter Effluent Booster Pump Effluent UV lamp I CTO Filter II Resin Filter III CTO Filter Municipal Water Input Clean Water Outlet Valve Top Tank Discharge Outlet UV Ballast ...

Страница 7: ...ol panel description as shown below labelling will be in English or Spanish Screen Display Function Button 13 15 16 17 1 2 3 4 5 6 7 8 9 10 11 12 14 18 19 20 21 Indicator Light Control Button Water Output Button ...

Страница 8: ...g 15 Humidity indicator indicating current humidity value 16 Booster pump icon the icon lights on means normal icon flashing means the pump is working 17 UV warning icon icon lights on means normal if it blinks means UV light is working 18 Bottom tank UV light indicator icon light on means normal if it flashes top tank UV light is functioning 19 Reflux UV light icon icon light on means normal if i...

Страница 9: ...rval should not be less than 8 minutes and start up cannot exceed 6 times one hour otherwise the compressor would suffer damage 3 3 Press STOP button to switch off the machine RUN indicator will be off When the machine is to be turned off in emergency press E STOP button Turn E STOP button clockwise to recover power supply 3 4 When display screen WARNNING icon is flashing it means unit failure It ...

Страница 10: ...from top tank to water output valve 11 If the machine is to be run again after it has been stopped for over 3 days about 20 liters of the initially generated water should be drained off to clean the filtration system 12 Cleaning the bottom tank and bottom filter is required once a month at least and the water in bottom tank should be removed Attention Before the cleaning switch off the machine the...

Страница 11: ... organic solvent e g Lacquer Thinner or other solvents containing acid or alkali to clean the painted surface 6 Air filter should be cleaned regularly subject to the local working conditions Normally it should be cleaned once a week Use soft brush to clear dust first and then clean with water or detergent Dry it in room air See Annex III 7 Always check the condenser if there is dust or dirt on the...

Страница 12: ...and reset the thermal relay after elimination Loose contact in contact or coil burnt Check the contacts Repair or replace Winding coil burnt or short circuit in motor Use megameter to measure the insulation between the phases Use multimeter to measure the winding resistance Repair or replace compressor Too low a voltage Buzzing in motor Use multimeter to measure winding resistance Increase the vol...

Страница 13: ...d Replacement of thermal relay Set to fit value Loud noise when working Fan blades touch the cover Check the fan blades touch Repair Fan motor bearing worn away Check the bearing Repair or replace Loosing in certain fixing part Check fixing parts Tighten Liquid impact inside compressor Sound of the impact to cylinder Decrease cooing gas amount Shut down the expansion valve Centrifugal fan motor bu...

Страница 14: ...e pump is working the flow sensor is broken if the pump stop working then Replace the flow sensor UV warning Breakdown in UV ballast Connect with external power to see if the bulb is burnt or not Replace the ballast and restart Breakdown in UV bulb Check the filaments at two ends if they became black or not Connect with external power to check it is burnt out or not Replace UV bulb and restart UV ...

Страница 15: ...f clip as per Picture Ⅰ 1 5 2 Remove the tubing of RO as per Picture Ⅰ 1 6 3 Remove cartridge cover as per Picture Ⅰ 1 7 and pull out RO membrane 4 Clean the internal cartridge wall with water 5 Pull out the old RO membrane picture 1 1 8 Soak the membrane in lemon solution 0 3 for 2 hours Flush with clean water 6 Replace the cleaned membrane or new membrane back into the cartridge Pay attention to...

Страница 16: ... and remove the fixer plate of UV sterilization device Picture Ⅰ 2 5 3 Remove UV wiring Picture Ⅰ 2 6 and sensor wiring Picture Ⅰ 2 7 4 Pull out the old bulb Picture Ⅰ 2 8 and replace with a new one 5 Reconnect the wiring and locked the UV device back to position 3 Replace UV bulb in bottom tank 1 Cut off master power of the machine and pull out bottom tank Ultraviolet lamp and water level probe s...

Страница 17: ... 16 Ⅰ 2 1 Ⅰ 2 2 Ⅰ 2 3 Ⅰ 2 4 Ⅰ 2 5 Ⅰ 2 6 Ⅰ 2 7 Ⅰ 2 8 ...

Страница 18: ...take out picture 1 3 1 post active carbon out picture I 3 2 replace filter cup back to sterilize filter cup 3 Open top cover and tank cover handle with care to avoid damage to water level sensor and UV Fill the solution prepared into top tank and replace back tank cover 4 Disconnect the connectors of top tank water level sensor wiring picture I 3 2 and short them with short piece of wire Picture Ⅰ...

Страница 19: ... Normally twice the operation is enough Replace back tank cover and top cover PIN Annex II When low voltage protection of compressor on machine displays on screen LOWER PRESSER OF COMPRESSOR PLS REPAIR AND RESTART Reasons need to be identified and eliminated before restarting When high Pressure Protection of Compressor When showing on Machine Display Screen HIGH PRESURE OF COMPRESSOR PLS REPAIR AN...

Страница 20: ... soft brush Picture Ⅱ 1 2 Wash the filter with clean water Picture Ⅱ 1 3 Dry the air filter and replace back to the machine 3 Cleaning period as per pollution level of air filter net normally once a week is enough Ⅲ 3 1 Ⅲ 3 2 Ⅲ 3 3 World Environmental Solutions Pty Ltd Australia www Multigensolutions com au Brisbane Australia END ...

Отзывы: